| 2022-11-30 15:11:52 | 9 STORY PARKING GARAGE |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE PROVIDE A SOIL REPORT FBC 1803 |
| | |
| | 2) DRAWING A6-100 - PLEASE SHOW THE AMBULANCE STRETCHER |
| | DIMENSIONS IN THE ELEVATOR PER FBC 3002.4 ELEVATOR CAR |
| | TO ACCOMMODATE AMBULANCE STRETCHER. |
| | ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN |
| | WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL |
| | LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET |
| | (7620 MM), MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE |
| | PASSENGER ELEVATOR THAT IS OPERATIONAL FOR BUILDING |
| | OCCUPANTS AND FIRE DEPARTMENT EMERGENCY ACCESS TO ALL |
| | FLOORS. THE ELEVATOR CAR SHALL BE OF SUCH A SIZE AND |
| | ARRANGEMENT TO ACCOMMODATE AN AMBULANCE STRETCHER 24 |
| | INCHES BY 76 INCHES (610 MM BY 1950 MM) WITH NOT LESS |
| | THAN 5-INCH (127 MM) RADIUS CORNERS, IN THE HORIZONTAL, |
| | OPEN POSITION AND SHALL BE IDENTIFIED BY THE |
| | INTERNATIONAL SYMBOL FOR EMERGENCY MEDICAL SERVICES |
| | (STAR OF LIFE). THE SYMBOL SHALL BE NOT LESS THAN 3 |
| | INCHES (76 MM) IN HEIGHT AND SHALL BE PLACED INSIDE ON |
| | BOTH SIDES OF THE HOISTWAY DOOR FRAME. |
| | |
| | 3) PLEASE PROVIDE THE STAIR SMOKE CONTROL DETAILS - FBC |
| | 909.4 ANALYSIS. |
| | A RATIONAL ANALYSIS SUPPORTING THE TYPES OF SMOKE |
| | CONTROL SYSTEMS TO BE EMPLOYED, THEIR METHODS OF |
| | OPERATION, THE SYSTEMS SUPPORTING THEM AND THE METHODS |
| | OF CONSTRUCTION TO BE UTILIZED SHALL ACCOMPANY THE |
| | SUBMITTED CONSTRUCTION DOCUMENTS AND SHALL INCLUDE, BUT |
| | NOT BE LIMITED TO, THE ITEMS INDICATED IN SECTIONS |
| | 909.4.1 THROUGH 909.4.7. |
| | |
| | 4) PLEASE PROVIDE THE ELEVATOR SHAFT PRESSURIZATION |
| | DETAILS - FBC 909.21.2 RATIONAL ANALYSIS. |
| | A RATIONAL ANALYSIS COMPLYING WITH SECTION 909.4 SHALL |
| | BE SUBMITTED WITH THE CONSTRUCTION DOCUMENTS. |
| | |
| | 5) PLEASE SHOW RESTROOM WALL FINISHES TO COMPLY WITH |
| | FBC 1210.2.2 WALLS AND PARTITIONS. |
| | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE |
| | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| | THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT |
| | CONSIDERED A HARD SURFACE) |
| | |
| | 6) PLEASE SHOW THE WALL FINISH SURROUNDING THE MOP SINK |
| | TO COMPLY WITH FBC 1210.2.2 WALLS AND PARTITIONS. |
| | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE |
| | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| | THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT |
| | CONSIDERED A HARD SURFACE) |
| | |
| | 7) DRAWING A3-300 - DETAILS 6 AND 9 SAY "TREADS" SHOULD |
| | SAY "RISERS" |
| | |
| | 8) DRAWING A3-300 - DETAILS SHOWING TREADS SHOULD SHOW |
| | THE TREAD WIDTHS - FBC 1011.5.2 |
| | |
| | 9) DRAWING A3-301 - DETAILS 2,7,4,1, NEED TO SHOW THE |
| | TREAD WIDTHS - FBC 1011.5.2 |
| | |
| | 10) DRAWING A3-302 - DETAILS 6 AND 8 - NEED TO SHOW THE |
| | TREAD WIDTHS - FBC 1011.5.2 |
| | |
| | 11) DRAWING A3-302 - DETAILS 9 AND 10 - SAYS "TREADS" |
| | SHOULD SAY "RISERS". |
| | |
| | 12) DRAWING A3-303 DETAIL 4 - PLEASE SHOW THE TREAD |
| | WIDTHS - FBC 1011.5.2 |
| | |
| | 13) DRAWING A3-305 DETAIL 3 AND 6 - SAYS "TREADS" |
| | SHOULD SAY "RISERS". |
| | |
| | 14) LIFE SAFETY DRAWINGS NEED TO SHOW STAIR ENCLOSURE |
| | "NS02" AS FIRE RATED FBC 713.4 |
| | |
| | 15) PLEASE PROVIDE THE "OPEN GARAGE" VENTILATION |
| | CALCULATIONS FOR EACH TIER PER - FBC 406.5.2 OPENINGS. |
| | FOR NATURAL VENTILATION PURPOSES, THE EXTERIOR SIDE OF |
| | THE STRUCTURE SHALL HAVE UNIFORMLY DISTRIBUTED OPENINGS |
| | ON TWO OR MORE SIDES. THE AREA OF SUCH OPENINGS IN |
| | EXTERIOR WALLS ON A TIER SHALL BE NOT LESS THAN 20 |
| | PERCENT OF THE TOTAL PERIMETER WALL AREA OF EACH TIER. |
| | THE AGGREGATE LENGTH OF THE OPENINGS CONSIDERED TO BE |
| | PROVIDING NATURAL VENTILATION SHALL BE NOT LESS THAN 40 |
| | PERCENT OF THE PERIMETER OF THE TIER. INTERIOR WALLS |
| | SHALL BE NOT LESS THAN 20 PERCENT OPEN WITH UNIFORMLY |
| | DISTRIBUTED OPENINGS. |
| | |
| | 16) PLEASE SHOW THE WINDOW AND DOOR OPENING WIND DESIGN |
| | PRESSURES - FBC 1603.1.4 |
| | |
| | 17) PLEASE SHOW THE ROOFING SYSTEMS AND THE REQUIRED |
| | WIND DESIGN PRESSURES - FBC 1609.5.1 |
| | |
| | 18) PLEASE SHOW ROOF DRAINAGE - FBC 1503.4 |
| | |
| | 19) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) FOR THE EXTERIOR WINDOWS, |
| | DOORS AND ROOFING SYSTEMS - ALL PRODUCT APPROVALS NEED |
| | TO BE REVIEWED AND MARKED APPROVED BY THE BUILDING |
| | DESIGNER OF RECORD (UNLESS LISTED ON THE DRAWINGS) - |
| | FBC WPB 107.3.4 |
| | |
| | 20) DRAWING S000 SHOWS WIND DESIGN SPEED AS 130 - |
| | SHOULD BE ALT 170 MPH PER FBC WPB SECTION 120 |
| | |
| | 21) WIND DESIGN CALCULATION PROVIDED SHOW ASCE 7-10 |
| | USED FOR WIND DESIGN - SHOULD BE ASCE 7-16 PER FBC |
| | CHAPTER 35 |
| | |
| | 22) THRESHOLD BUILDING - PROVIDE THE FOLLOWING |
| | STATEMENT ON THE DRAWINGS - FBC WPB 110.8.4.4 ALL PLANS |
| | FOR THE BUILDING WHICH ARE REQUIRED TO BE SIGNED AND |
| | SEALED |
| | BY THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A |
| | STATEMENT THAT, TO THE BEST OF THE ARCHITECT'S OR |
| | ENGINEER'S KNOWLEDGE, THE PLANS AND SPECIFICATIONS |
| | COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND |
| | THE APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY |
| | THE LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND |
| | CHAPTER 633. FLORIDA STATUTES. |
| | |
| | 23) THRESHOLD BUILDING - SPECIAL INSPECTOR FORMS NEED |
| | TO BE FILLED OUT - PLEASE READ AND FILL OUT THE |
| | REQUIRED DOCUMENTS PER THE "GUIDELINES AND POLICIES FOR |
| | PROJECTS CONCERNING THRESHOLD/SPECIAL INSPECTORS AND |
| | RESIDENT INSPECTORS". YOU CAN E MAIL ME AND ASK FOR A |
| | COPY. |
| | |
| | 24) ADA DETAILS SHOWN ON DRAWING A0-004 - PLEASE SHOW |
| | THE TOILET REAR GRAB BAR LOCATION DIMENSIONS FROM THE |
| | CENTER OF THE TOILET - FBC A 604.5.2 REAR WALL. |
| | THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 |
| | INCHES (610 MM) MINIMUM ON THE OTHER SIDE. |
| | |
| | 25) ADA DETAILS SHOWN ON DRAWING A0-004 - PLEASE SHOW |
| | THE TOILET PAPER HOLDER LOCATION DIMENSIONS FROM THE |
| | FACE OF THE TOILET PER FBC A 604.7 DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF THE DISPENSER. |
| | |
| | 26) ADA DETAILS SHOWN ON DRAWING A0-004 - PLEASE SHOW |
| | THE MAXIMUM HEIGHT OF THE GRAB BARS TO THE TOP OF THE |
| | GRIPPING SURFACE NOT THE CENTER OF THE BAR AS SHOWN - |
| | FBC A 609.4 POSITION OF GRAB BARS. |
| | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, |
| | 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) |
| | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| | THE GRIPPING SURFACE, |
| | |
| | 27) ADA DETAILS SHOWN ON DRAWING A0-004 - PLEASE USE |
| | THE WORDS "REFLECTIVE SURFACE" WHEN REFERRING TO THE |
| | DIMENSION FROM THE FLOOR TO THE BOTTOM OF THE MIRROR - |
| | FBC A 603.3 MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | |
| | 28) DRAWING A0-002 SHOWS 4 ACCESSIBLE PARKING SPACES ON |
| | 2ND FLOOR - THE PARKING CALCS. SAY 2 - (3RD THROUGH 8TH |
| | FLOORS SHOW 5 BUT THE PARKING CALCS. SHOW 4) - PLEASE |
| | CLARIFY - THE A1 FLOOR PLANS PROVIDED NEED TO MATCH |
| | A0-002 |
| | |
| | 29) DRAWING A1-200 - PARKING SPACE "005" PLEASE SHOW |
| | THE ACCESSIBLE ROUTE TO AN ENTRY FROM THE PARKING |
| | ACCESS AISLE THAT DOESN'T LEAD BEHIND ANOTHER PARKED |
| | CAR FBC A 208.3.1 ALL SPACES MUST BE LOCATED ON AN |
| | ACCESSIBLE ROUTE THAT IS AT LEAST 44 INCHES (1118 MM) |
| | WIDE AND SO THAT USERS ARE NOT COMPELLED TO WALK OR |
| | WHEEL BEHIND PARKED VEHICLES EXCEPT BEHIND HIS OR HER |
| | OWN VEHICLE. |
| | |
| | 30) 1) DRAWINGS LS-1, S000,S001, S002, S100, S101, |
| | S102, S103, S104,S105, S107, S108, S109, S110, S111, |
| | S112, S115, S116, S200, S300, S400, S501, S601, S602 DO |
| | NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER - |
| | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE |
| | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN |
| | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL |
| | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A |
| | SPECIFIC TYPE OF E-SIGNATURE). |
| | |