Date Text
2022-11-30 15:11:529 STORY PARKING GARAGE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A SOIL REPORT FBC 1803
  
 2) DRAWING A6-100 - PLEASE SHOW THE AMBULANCE STRETCHER
 DIMENSIONS IN THE ELEVATOR PER FBC 3002.4 ELEVATOR CAR
 TO ACCOMMODATE AMBULANCE STRETCHER.
 ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL
 LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET
 (7620 MM), MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE
 PASSENGER ELEVATOR THAT IS OPERATIONAL FOR BUILDING
 OCCUPANTS AND FIRE DEPARTMENT EMERGENCY ACCESS TO ALL
 FLOORS. THE ELEVATOR CAR SHALL BE OF SUCH A SIZE AND
 ARRANGEMENT TO ACCOMMODATE AN AMBULANCE STRETCHER 24
 INCHES BY 76 INCHES (610 MM BY 1950 MM) WITH NOT LESS
 THAN 5-INCH (127 MM) RADIUS CORNERS, IN THE HORIZONTAL,
 OPEN POSITION AND SHALL BE IDENTIFIED BY THE
 INTERNATIONAL SYMBOL FOR EMERGENCY MEDICAL SERVICES
 (STAR OF LIFE). THE SYMBOL SHALL BE NOT LESS THAN 3
 INCHES (76 MM) IN HEIGHT AND SHALL BE PLACED INSIDE ON
 BOTH SIDES OF THE HOISTWAY DOOR FRAME.
  
 3) PLEASE PROVIDE THE STAIR SMOKE CONTROL DETAILS - FBC
 909.4 ANALYSIS.
 A RATIONAL ANALYSIS SUPPORTING THE TYPES OF SMOKE
 CONTROL SYSTEMS TO BE EMPLOYED, THEIR METHODS OF
 OPERATION, THE SYSTEMS SUPPORTING THEM AND THE METHODS
 OF CONSTRUCTION TO BE UTILIZED SHALL ACCOMPANY THE
 SUBMITTED CONSTRUCTION DOCUMENTS AND SHALL INCLUDE, BUT
 NOT BE LIMITED TO, THE ITEMS INDICATED IN SECTIONS
 909.4.1 THROUGH 909.4.7.
  
 4) PLEASE PROVIDE THE ELEVATOR SHAFT PRESSURIZATION
 DETAILS - FBC 909.21.2 RATIONAL ANALYSIS.
 A RATIONAL ANALYSIS COMPLYING WITH SECTION 909.4 SHALL
 BE SUBMITTED WITH THE CONSTRUCTION DOCUMENTS.
  
 5) PLEASE SHOW RESTROOM WALL FINISHES TO COMPLY WITH
 FBC 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
  
 6) PLEASE SHOW THE WALL FINISH SURROUNDING THE MOP SINK
 TO COMPLY WITH FBC 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
  
 7) DRAWING A3-300 - DETAILS 6 AND 9 SAY "TREADS" SHOULD
 SAY "RISERS"
  
 8) DRAWING A3-300 - DETAILS SHOWING TREADS SHOULD SHOW
 THE TREAD WIDTHS - FBC 1011.5.2
  
 9) DRAWING A3-301 - DETAILS 2,7,4,1, NEED TO SHOW THE
 TREAD WIDTHS - FBC 1011.5.2
  
 10) DRAWING A3-302 - DETAILS 6 AND 8 - NEED TO SHOW THE
 TREAD WIDTHS - FBC 1011.5.2
  
 11) DRAWING A3-302 - DETAILS 9 AND 10 - SAYS "TREADS"
 SHOULD SAY "RISERS".
  
 12) DRAWING A3-303 DETAIL 4 - PLEASE SHOW THE TREAD
 WIDTHS - FBC 1011.5.2
  
 13) DRAWING A3-305 DETAIL 3 AND 6 - SAYS "TREADS"
 SHOULD SAY "RISERS".
  
 14) LIFE SAFETY DRAWINGS NEED TO SHOW STAIR ENCLOSURE
 "NS02" AS FIRE RATED FBC 713.4
  
 15) PLEASE PROVIDE THE "OPEN GARAGE" VENTILATION
 CALCULATIONS FOR EACH TIER PER - FBC 406.5.2 OPENINGS.
 FOR NATURAL VENTILATION PURPOSES, THE EXTERIOR SIDE OF
 THE STRUCTURE SHALL HAVE UNIFORMLY DISTRIBUTED OPENINGS
 ON TWO OR MORE SIDES. THE AREA OF SUCH OPENINGS IN
 EXTERIOR WALLS ON A TIER SHALL BE NOT LESS THAN 20
 PERCENT OF THE TOTAL PERIMETER WALL AREA OF EACH TIER.
 THE AGGREGATE LENGTH OF THE OPENINGS CONSIDERED TO BE
 PROVIDING NATURAL VENTILATION SHALL BE NOT LESS THAN 40
 PERCENT OF THE PERIMETER OF THE TIER. INTERIOR WALLS
 SHALL BE NOT LESS THAN 20 PERCENT OPEN WITH UNIFORMLY
 DISTRIBUTED OPENINGS.
  
 16) PLEASE SHOW THE WINDOW AND DOOR OPENING WIND DESIGN
 PRESSURES - FBC 1603.1.4
  
 17) PLEASE SHOW THE ROOFING SYSTEMS AND THE REQUIRED
 WIND DESIGN PRESSURES - FBC 1609.5.1
  
 18) PLEASE SHOW ROOF DRAINAGE - FBC 1503.4
  
 19) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) FOR THE EXTERIOR WINDOWS,
 DOORS AND ROOFING SYSTEMS - ALL PRODUCT APPROVALS NEED
 TO BE REVIEWED AND MARKED APPROVED BY THE BUILDING
 DESIGNER OF RECORD (UNLESS LISTED ON THE DRAWINGS) -
 FBC WPB 107.3.4
  
 20) DRAWING S000 SHOWS WIND DESIGN SPEED AS 130 -
 SHOULD BE ALT 170 MPH PER FBC WPB SECTION 120
  
 21) WIND DESIGN CALCULATION PROVIDED SHOW ASCE 7-10
 USED FOR WIND DESIGN - SHOULD BE ASCE 7-16 PER FBC
 CHAPTER 35
  
 22) THRESHOLD BUILDING - PROVIDE THE FOLLOWING
 STATEMENT ON THE DRAWINGS - FBC WPB 110.8.4.4 ALL PLANS
 FOR THE BUILDING WHICH ARE REQUIRED TO BE SIGNED AND
 SEALED
 BY THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A
 STATEMENT THAT, TO THE BEST OF THE ARCHITECT'S OR
 ENGINEER'S KNOWLEDGE, THE PLANS AND SPECIFICATIONS
 COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND
 THE APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY
 THE LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND
 CHAPTER 633. FLORIDA STATUTES.
  
 23) THRESHOLD BUILDING - SPECIAL INSPECTOR FORMS NEED
 TO BE FILLED OUT - PLEASE READ AND FILL OUT THE
 REQUIRED DOCUMENTS PER THE "GUIDELINES AND POLICIES FOR
 PROJECTS CONCERNING THRESHOLD/SPECIAL INSPECTORS AND
 RESIDENT INSPECTORS". YOU CAN E MAIL ME AND ASK FOR A
 COPY.
  
 24) ADA DETAILS SHOWN ON DRAWING A0-004 - PLEASE SHOW
 THE TOILET REAR GRAB BAR LOCATION DIMENSIONS FROM THE
 CENTER OF THE TOILET - FBC A 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 25) ADA DETAILS SHOWN ON DRAWING A0-004 - PLEASE SHOW
 THE TOILET PAPER HOLDER LOCATION DIMENSIONS FROM THE
 FACE OF THE TOILET PER FBC A 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  
 26) ADA DETAILS SHOWN ON DRAWING A0-004 - PLEASE SHOW
 THE MAXIMUM HEIGHT OF THE GRAB BARS TO THE TOP OF THE
 GRIPPING SURFACE NOT THE CENTER OF THE BAR AS SHOWN -
 FBC A 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
  
 27) ADA DETAILS SHOWN ON DRAWING A0-004 - PLEASE USE
 THE WORDS "REFLECTIVE SURFACE" WHEN REFERRING TO THE
 DIMENSION FROM THE FLOOR TO THE BOTTOM OF THE MIRROR -
 FBC A 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 28) DRAWING A0-002 SHOWS 4 ACCESSIBLE PARKING SPACES ON
 2ND FLOOR - THE PARKING CALCS. SAY 2 - (3RD THROUGH 8TH
 FLOORS SHOW 5 BUT THE PARKING CALCS. SHOW 4) - PLEASE
 CLARIFY - THE A1 FLOOR PLANS PROVIDED NEED TO MATCH
 A0-002
  
 29) DRAWING A1-200 - PARKING SPACE "005" PLEASE SHOW
 THE ACCESSIBLE ROUTE TO AN ENTRY FROM THE PARKING
 ACCESS AISLE THAT DOESN'T LEAD BEHIND ANOTHER PARKED
 CAR FBC A 208.3.1 ALL SPACES MUST BE LOCATED ON AN
 ACCESSIBLE ROUTE THAT IS AT LEAST 44 INCHES (1118 MM)
 WIDE AND SO THAT USERS ARE NOT COMPELLED TO WALK OR
 WHEEL BEHIND PARKED VEHICLES EXCEPT BEHIND HIS OR HER
 OWN VEHICLE.
  
 30) 1) DRAWINGS LS-1, S000,S001, S002, S100, S101,
 S102, S103, S104,S105, S107, S108, S109, S110, S111,
 S112, S115, S116, S200, S300, S400, S501, S601, S602 DO
 NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER -
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  