Plan Review Notes
Plan Review Notes For Permit 22101231
Permit Number 22101231
Review Stop M
Sequence Number 1
Notes
Date Text
2022-11-08 06:23:281) THIIS PERMIT IS FOR THE WALK-IN COOLER BUT THERE WAS
 NOTHING SUBMITTED FOR THE WALK-IN COOLER. THERE ARE 2
 DIFFERENT DRAWINGS ONE SHOWING THE COOLER UP AGAINST
 THE STAIR WALL WITH THE ENTRANCE TO THE COOLER THROUUGH
 A DOOR UNDER THE STAIRS AND ANOTHER DRAWING SHOWING THE
 COOLER AWAY FROM THE WALL WITH THE GLYCOL COOLERS
 SITTING BEHIND THE COOLER. PLEASE SUBMIT THE ONE
 DRAWING THAT WILL BE ACCURATE TO THE TRUE LAYOUT OF THE
 COOLER. FBC 107.3.5
 2) THE WALK-IN COOLER REFRIGERATION SYSTEM MUST MEET
 FMC 1102. PROVIDE THE FOLLOWING INFORMATION FOR THIS
 COOLER.
  
 1102.1 GENERAL. THE SYSTEM CLASSIFICATION, ALLOWABLE
 REFRIGERANTS,
 MAXIMUM QUANTITY, ENCLOSURE REQUIREMENTS, LOCATION
 LIMITATIONS, AND FIELD PRESSURE TEST REQUIREMENTS SHALL
 BE
 DETERMINED AS FOLLOWS:
 1. DETERMINE THE REFRIGERATION SYSTEM'S CLASSIFICATION,
 IN
 ACCORDANCE WITH SECTION 1103.3.
 2. DETERMINE THE REFRIGERANT CLASSIFICATION IN
 ACCORDANCE
 WITH SECTION 1103.1.
 3. DETERMINE THE MAXIMUM ALLOWABLE QUANTITY OF
 REFRIGERANT
 IN ACCORDANCE WITH SECTION 1104, BASED ON TYPE OF
 REFRIGERANT, SYSTEM CLASSIFICATION AND OCCUPANCY.
 4. DETERMINE THE SYSTEM ENCLOSURE REQUIREMENTS IN
 ACCORDANCE
 WITH SECTION 1104.
 5. REFRIGERATION EQUIPMENT AND APPLIANCE LOCATION AND
 INSTALLATION SHALL BE SUBJECT TO THE LIMITATIONS OF
 CHAPTER
 3.
 6. NONFACTORY-TESTED, FIELD-ERECTED EQUIPMENT AND
 APPLIANCES
 SHALL BE PRESSURE TESTED IN ACCORDANCE WITH SECTION
 1108.