| Plan Review Notes For Permit 22101216 |
| Permit Number |
22101216 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-10-28 11:36:41 | FIRE PROVISO COMMENTS: | | | | | | (1) ANY IMPAIRMENT TO THE FIRE ALARM SYSTEM THAT | | | EXCEEDS 4 CONTINUOUS HOURS IN DURATION SHALL REQUIRE | | | THE IMPLEMENTATION OF A FIRE WATCH. | | | | | | (2) DUCT DETECTORS SHALL BE PROGRAMMED TO REPORT IN | | | SUPERVISORY MODE. | | | | | | (3) WITNESSED TEST OF DEVICES AFTER INSTALLATION AND A | | | RECORD OF COMPLETION TO BE SUBMITTED TO THE FIRE | | | DEPARTMENT INSPECTOR. | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|