| 2022-11-29 12:35:14 | 1ST BUILDING REVIEW |
| | RESULTS: CORRECTIONS NEEDED |
| | |
| | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM |
| | PLANS EXAMINER II |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | NFPA 70 2017 EDITION NEC 2017 |
| | |
| | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: |
| | |
| | NOTICE: A SEPERATE PERMIT IS REQUIRED FOR THE GUEST |
| | HOUSE. ALL PLANS MAY REMAIN UNDER THE MAIN DWELLING |
| | UNIT (22101205). PERMITS SHALL TRAVEL TOGETHER. |
| | |
| | 1. REFERENCE PLAN PAGE 1 OF 1 FOR THE FOLLOWING: |
| | 1A) CONSTRUCTION TYPE IS STATED AS TYPE IIIB. TYPE IIB |
| | CONSTRUCTION SHALL BE DESIGNED PER THE FBC CHPT. 16 |
| | AND/OR ASCE 7-16 WITH RATED EXTERIOR WALLS. |
| | CONSTRUCTION TYPE FOR THIS STRUCTURE IS TYPE VB AND CAN |
| | BE DESIGNED PER FBC RESIDENTIAL CHAPTER 3. |
| | 1B) OCCUPANCY IS STATED AS GROUP VB. THE OCCUPANCY |
| | CLASSIFICATION PER FBC CHPT 3, SECTION 310 IS |
| | RESIDENTIAL GROUP R-3. |
| | 1C) NEW DECK IS MISSING FROM THE SCOPE OF WORK (SOW). |
| | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE |
| | WITH SECTIONS107.2.1 THROUGH 107.2.5. |
| | |
| | 2. PROVIDE AN EXISTING FLOOR PLAN FOR BOTH STRUCTURES. |
| | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE |
| | WITH SECTIONS107.2.1 THROUGH 107.2.5. |
| | |
| | 3. PROVIDE REQUIRED DEMENSIONS ON PROPOSED FLOOR PLANS. |
| | VERIFY CLEARANCES IN BATHROOMS. |
| | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE |
| | WITH SECTIONS107.2.1 THROUGH 107.2.5. |
| | |
| | 4.PROVIDE A COPY OF THE MOST RECENT BOUNDARY LINE |
| | SURVEY. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 5. PROVIDE A SITE PLAN.... |
| | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED |
| | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY |
| | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF |
| | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, |
| | AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE |
| | AND INCLUDED BOUNDARY LINE SURVEY. |
| | |
| | 6. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 |
| | IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| | INCLUDED BOUNDARY LINE SURVEY. |
| | FBC R401.3 SITE DRAINAGE |
| | |
| | 7.PROVIDE SMOKE ALARMS. |
| | FBC 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A |
| | BUILDING. |
| | SMOKE ALARMS |
| | R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE |
| | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| | LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC R314. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | |
| | |