2022-11-04 07:38:301ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22101172
 11/4/22
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 2: THE EXISTING POOL HAS INCREASED IN SQUARE
 FOOTAGE AND VOLUME. PLEASE PROVIDE REVISED POOL DATA
 INCLUDING TOTAL SQUARE FOOTAGE, TOTAL POOL VOLUME,
 RECIRCULATION TURNOVER RATE- SEC. R4501.6 FBC RES.
  
 2) SHEET 2: THE PIPING SCHEMATIC SHOWING ONE PUMP FOR
 BOTH THE POOL AND THE SPA DOESN???T MATCH THE APPROVED
 POOL PLANS UNDER PERMIT 17040402 WHICH SHOWS SEPARATE
 PUMPS FOR THE POOL AND SPA- SEC. R4501.6 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  