Plan Review Notes
Plan Review Notes For Permit 22101147
Permit Number 22101147
Review Stop P
Sequence Number 1
Notes
Date Text
2022-11-03 16:22:491ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22101147
 11/3/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P-0, P-2 & P-3: PLEASE PROVIDE AN ENLARGED
 WATER PIPING DETAIL FOR THE WATER HEATER SHOWING THE
 NEW RECIRCULATION PUMP AND MASTER THERMOSTATIC MIXING
 VALVE PIPE CONNECTIONS- SECS. 607.1.1 & 607.2.2 FBC P.
 PLEASE NOTE THE MASTER TMV IS MANDATORY.
  
 A) PLEASE SHOW THE LOCATION OF AND TYPE OF THERMAL
 EXPANSION CONTROL DEVICE IN THE WH PIPING DETAIL- SEC.
 607.3 FBC P.
  
 B) PROVIDE THE TYPE AND THICKNESS OF HW PIPE
 INSULATION- TABLE C403.2.10 FBC EC.
  
 2) P0, P-2, P-3: SHOW THE MEANS OF PROVIDING TEMPERED
 WATER DELIVERY FROM THE PUBLIC LAVATORIES- SEC. 419.5
 FBC P. PLEASE NOTE MIXING VALVES USED FOR TEMPERED
 WATER SHALL BE ASSE 1070 APPROVED- SEC. 607.1.2.
  
 3) A-1.0: PLEASE SHOW THE 30X48-INCH CLEAR FLOOR SPACE
 DIAGRAM AT EACH ACCESSIBLE SINK LOCATION- SEC. 606.2
 FBC ACC.
  
 4) A-4.1 ELEV. B: SHOW THE MINIMUM KNEE 27-INCH
 CLEARANCE HEIGHT FROM THE F.F.- FIGURE 306.3 FBC ACC.
  
 5) A-4.3 DET. 2: PLEASE CORRECT THE FOLLOWING ITEMS PER
 THE FBC ACC
  
 A) SHOW THE HEIGHT OF THE GRAB BARS MEASURED TO THE
 TOPS OF THE GRIPPING SURFACES- SEC. 609.4.
  
 B) SHOW THE CENTERLINE OF THE TOILET PAPER DISPENSER IS
 AT 7-9-INCHES MEASURED FROM THE FRONT OF THE WATER
 CLOSETS SEC. 604.7. THE DETAIL DOES NOT SHOW THE
 MEASUREMENT TO THE CENTER OF THE DISPENSER OUTLET.
  
 C) SHOW THE HEIGHTS OF THE MIRRORS FROM THE F.F. TO THE
 REFLECTIVE SURFACES- SEC. 603.3.
  
 6) A-4.1 & A-4.3: SHOW THE CLEAR FLOOR SPACE DIAGRAM AT
 THE ACCESSIBLE DRINKING FOUNTAIN LOCATION- SEC. 602.2
 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER