2022-11-11 08:49:311ST REVIEW FMC
 PERMIT: 22101147
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW ON THE LIFE SAFETY PLAN HOW THIS
 OCCUPANT WILL MEET THE OFFICE SURGERY SUITE OCCUPANCY
 CLASSIFICATION IN FBC 469.3
  
 2) SHEET M-1: IDENTIFY THE ROOM TO THE LEFT OF
 PROCEDURE ROOM 1.
  
 3) SHEET M-1: PROVIDE THE DUCT SIZES AT EACH DUCT. FBC
 107.3.5
  
 4) SHEET M-1: PROVIDE THE REQUIRED SMOKE DUCT DETECTOR
 IN THE NEW AHU. FMC 606.2.2
  
 5) PROVIDE AN OUTDOOR AIR CALCULATIONS FOR EACH SPACE
 IN EACH ZONE. USE THE OCCUPANCY CLASSIFICATION THAT
 MOST CLOSELY RESEMBLES THE USE OF SPACE IN TABLE
 403.3.1.1. FMC 403.3.1.1 AND TABLE 403.3.1.1
  
 6) PROVIDE EXHAUST FANS THAT WOULD MEET THE MINIMUM OF
 70 CFM???S PER WATER CLOSET IF CONTROLLED
 INTERMITTENTLY. FMC TABLE 403.3.1.1 AND FOOTNOTE E
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  