| 2022-12-13 16:49:41 | 2ND REVIEW FMC | | | PERMIT: 22101146 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE DUCT LAYOUT SHEET IS NOT READABLE. PLEASE | | | PROVIDE A CLEAR AND READABLE MECHANICAL DUCT LAYOUT | | | DESIGN. FBC 107.3.5 | | | | | | 2) PLEASE RESPOND TO THE COMMENTS FROM THE 1ST REVIEW | | | CYCLE BELOW: | | | | | | 1) PROVIDE A COMPLETE SET OF MECHANICAL DRAWINGS | | | SHOWING WHY AN ADDITIONAL 15 TONS OF AIR IS NEEDED FOR | | | THIS TENANT SPACE. HAS THE CHANGE OF USE FOR THIS | | | TENANT CHANGED? I DO SEE ONLINE PICTURES OF A STAGE | | | THAT WAS NOT ON THE ORIGINAL APPROVED SUBMITTAL FOR | | | PERMIT 18021224. FBC 107.3.5 | | | | | | 2) PROVIDE THE COMPLETE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS, ONLY PAGE 1 WAS SUBMITTED. FEC C403.2.1 | | | | | | 3) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THIS NEW | | | SYSTEM. FMC 403.3.1.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|