| 2022-10-26 11:57:21 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION OF THE REPLACEMENT OF |
| | EXISTING MATERIAL; HOWEVER, THERE IS NO SITE PLAN |
| | SHOWING THE LOCATION OF THE EXISTING STRUCTURE. |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS. |
| | |
| | 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO |
| | THE ALTERATION OF THE MEANS OF EGRESS OR FIRE |
| | PROTECTION SYSTEMS OF ANY EXISTING BUILDING. |
| | |
| | 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER |
| | CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE |
| | COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDEA SITE PLAN |
| | INDICATING WHERE THE PROPOSED REPLACEMENT STRUCTURE IS |
| | LOCATED |
| | |
| | |
| | 2) PLEASE PROVIDE DETAILS IF THERE IS ANY ELECTRICAL |
| | WORK IS PROPOSED OR IS BEING SYBMITTED UNDER SEPARATE |
| | PERMIT. |
| | |
| | |
| | |
| | 3) PLEASE PROVIDE DETAILS IF THERE IS ANY EXITING |
| | THROUGH THIS AREA AND IF THE WORK WILL BE DONE WHILE |
| | THE OCCUPANCY IS OPEN. |
| | |
| | IF OPEN AND EXTING OCCURS THROUGH THIS AREA, PLEASE |
| | PROVIDE DETAILS FOR ALTERNATIVE EXITS/EXIT ROUTING. |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |