2022-11-30 11:57:21THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE REMAINS NO DETAIL OF THE PROPOSED CEILING
 ASSEMBLY.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE GREATER DETAIL
 FOR THE CEILING ASSEMBLY INCLUDING THE LISTED
 SPECIFICATIONS.
  
  
  
 2) THERE REMAINS NO DETAIL OF FIRE SPRINKLER HEAD
 LOCATION, CEILING NOR SIDEWALL.
  
 A LETTER FROM A FIRE SPRINKLER CONTRACTOR IS NEEDED TO
 ENSURE THE PROPOSED CEILING WORK DOES NOT AFFECT THE
 REQUIRED PROTECTION.
  
 THIS LETTER NEEDS TO BE AVAILABLE AT THE TIME OF FINAL
 FIRE INSPECTION TO PRESENT TO THE FIRE INSPECTOR FOR
 CONFIRMATION PURPOSES.
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE A NOTE OF
 ACKNOWLEDGMENT ON THE FLOOR PLAN.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  