Plan Review Notes
Plan Review Notes For Permit 22101072
Permit Number 22101072
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-11-02 11:47:05THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION ON THE APPLICATION OF "TILING
 A BEDROMM AND DEN USING 8" CONCRETE FLOOR WITH A GYPSUM
 BOARD CEILING ASSEMBLY."
  
 THERE IS NO FLOOR PLAN SUBMITTED THAT INDICATES THE
 LOCATION OF THE PROPOSED TILE NOR OF ANY PROPOSED
 CEILING ASSEMBLY.
  
 PER NFPA 101
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE A FLOOR PLAN
 INDICATING THE LOCATION OF ALL PROPOSED WORK.
  
  
  
 2) THERE IS AN INDICATION ON THE APPLICATION OF A
 CEILING ASSEMBLY, BUT NO CONSTRUCTION CALL-OUT OF WHAT
 THE ASSEMBLY CONSIST OF, FASTENING DEVICES, LISTING
 SPECIFICATIONS, FIRE SPRINKLER LOCATIONS/MODIFICATIONS,
 FIRE ALARM, SMOKE ALARM, ELECTRICAL WORK, ETC.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE A DETAILED
 DRAWING/PLAN OF THE CEILING ASSEMBLY AND ALL APPLICABLE
 SPECIFICATIONS.
  
  
 2A) ANY FIRE SPRINKLER WORK, INCLUDING DEMO, SHALL BE
 COMPLETED UNDER SEPARATE PERMIT AND SHOP DRAWINGS IN
 COMPLIANCE WITH NFPA 13.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGMENT.
  
  
  
 2B) ANY FIRE ALARM WORK, INCLUDING DEMO, SHALL BE
 COMPLETED UNDER SEPARATE PERMIT AND SHOP DRAWINGS IN
 COMPLIANCE WITH NFPA 13.
  
 PLEASE REVIEW AND IF APPLICABLE, ENSURE COMPLIANCE.
  
  
 2C) SMOKE ALARM MODIFICATIONS, RELOCATION, NEW
 INSTALLATIONS SHALL BE REFLECTED ON THE ELECTICAL
 DRAWING/PLAN.
  
 WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION
 CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  