| 2022-12-08 15:38:08 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC SEVENTH EDITION (2020) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE DRAWINGS INDICATE THAT THE SHED IS TO BE USED |
| | FOR STORAGE AND WILL NOT BE USED AS HABITABLE SPACE. |
| | THE SURVEY (DATED 8/15/1988) SHOWS THAT THE SHED WAS ON |
| | THE PROPERTY AT THAT TIME. THE PRINTED NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DRAWINGS IS |
| | REQUIRED TO BE ON THEM. FBC 107.2.1 - INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. |
| | |
| | 2) SPECIFY THE SIZE OF THE WINDOW AND DOOR OPENING IN |
| | THE EXISTING SHED ON THE PLANS. IF THE OPENINGS ARE |
| | MODIFIED TO ACCOMADATE THE NEW DOOR OR WINDOW, SUBMIT |
| | STRUCTURAL DRAWINGS FOR THE OPENINGS. FBC 107.2.1 |
| | |
| | 3) THE FLORIDA PRODUCT APPROVAL COVERSHEET IS MISSING |
| | FOR THE GLAZED DOOR. SUBMIT THE COMPLETE PRODUCT |
| | APPROVAL FOR THE DOOR. CIRCLE OR HI-LIGHT THE DOOR |
| | SIZE, GLASS TYPE AND DESIGN PRESSURES FOR THE DOOR ON |
| | THE PRODUCT APPROVAL.FBC 107.3.4 |
| | |
| | 4) CIRCLE OR HI-LIGHT THE WINDOW TYPE, DIMENSIONS AND |
| | DESIGN PRESSURES ON THE CHARTS IN THE WINDOW PRODUCT |
| | APPROVAL. FBC 107.2.1 |
| | |
| | 5) PROVIDE A FLASHING DETAIL TO SHOW HOW THE DOOR AND |
| | WINDOW IS GOING TO BE FLASHED. FBC 107.2.1 |
| | |
| | 6) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |
| | |