2022-12-22 13:49:31ELECTRIC REVIEW FAILED
 1) ORIGINAL RISER INDICATED (6) 1/0 CONDUCTORS FEEDING
 (2) PANELS. NEW RISER INDICATES ENTIRE LOAD WILL BE
 HANDLED BY (1) 150-AMP OCP. LOAD CALCULATIONS PROVIDED
 DO NOT INCLUDE ALL LOADS (HEAT, COOKTOPS ETC.). PLEASE
 PROVIDE ENTIRE SERVICE LOAD CALCULATIONS. USING EITHER
 THE STANDARD OR OPTIONAL METHOD,. INCLUDE ALL LOADS, IF
 LOADS ARE GAS, PLEASE INDICATE THEM AS SO. ALSO PROVIDE
 COMPLETE PANEL SCHEDULES FOR ALL (3) PANELS, MAIN
 DISCONNECT PANEL, PANEL A AND B. INCLUDE ALL OVER
 CURRENT PROTECTION SIZES. NEC 215.5
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  