Plan Review Notes
Plan Review Notes For Permit 22101029
Permit Number 22101029
Review Stop E
Sequence Number 1
Notes
Date Text
2022-12-01 08:35:46ELECTRIC REVIEW FAILED
 1) PLAN INDICATES (6) 1/0 CU CONDUCTORS FROM A 150- AMP
 MAIN BREAKER PANEL TO A 200-AMP TRANSFER SWITCH THEN TO
 (2) 150-AMP PANELS. PLEASE PROVIDE ADDITIONAL
 INFORMATION ON PLAN, SUCH AS WHERE DO ALL CONDUCTORS
 TERMINATE, WHAT LOADS WILL THE TRANSFER SWITCH FEED,
 ETC. NEC 215.5 FBC 107.2
  
 2) IN ADDITION, 1/0 CU CONDUCTOR AMPACITY IS 150- AMPS.
 THE REDUCTION IN AMPACITY AS PER NEC 310.15 (B)(7)(2)
 IS NOT APPLICABLE BECAUSE THESE CONDUCTORS DO NOT CARRY
 THE ENTIRE LOAD TO THE DWELLING. SINCE THERE ARE 6
 CONDUCTORS IN THE CONDUIT THE AMPACITY MUST BE REDUCED
 AS PER NEC TABLE 310.15(B)(3)(A). THESE CONDUCTORS AS
 SHOWN ARE NOT CODE COMPLIANT. PLEASE REVISE AS
 APPLICABLE FOR CODE COMPLIANCE
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved