| Plan Review Notes For Permit 22101024 |
| Permit Number |
22101024 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2023-05-22 07:55:58 | 3RD PLUMBING REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. CORRECTIONS DO NOT PROPERLY ADDRESS THE ISSUE - THE | | | LAUNDRY AND SINK CANNOT BE INCLUDED IN THE WET VENT | | | SYSTEM FOR THE BATHROOM GROUP FIXTURES. THEY MUST | | | DISCHARGE DOWNSTREAM OF THE WET VENT SYSTEM. | | | PLUMBING ISOMETRIC/UPSTAIRS BATHROOM GROUP - 2020 FRC | | | P3108.1 - THE LAUNDRY UPSTAIRS CANNOT CONNECT AT THE | | | SAME LOCATION AS THE BATHROOM GROUP FIXTURES. THE | | | LAUNDRY AND LAUNDRY SINK MUST DISCHARGE DOWNSTREAM OF | | | THE WET VENT SYSTEM. | | | | | | 2. DONE | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | |
|