| 2022-11-29 11:23:00 | 1ST PLUMBING REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. PLUMBING ISOMETRIC/UPSTAIRS BATHROOM GROUP - 2020 | | | FRC P3108.1 - THE LAUNDRY UPSTAIRS CANNOT CONNECT AT | | | THE SAME LOCATION AS THE BATHROOM GROUP FIXTURES. THE | | | LAUNDRY AND LAUNDRY SINK MUST DISCHARGE DOWNSTREAM OF | | | THE WET VENT SYSTEM. | | | | | | 2. PLUMBING ISOMETRIC/DOWNSTAIRS HALF BATH - 2020 FRC | | | P3108.1 - THE WATER CLOSET CANNOT CONNECT TO THE | | | BUILDING DRAIN WITHOUT A VENT. EITHER ADD A VENT FOR | | | THE WATER CLOSET OR CONNECT THE BATHROOM GROUP FIXTURE | | | (LAVATORY) TO THE WATER CLOSET FIXTURE DRAIN BEFORE IT | | | CONNECTS TO THE BUILDING DRAIN. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | |
|