Plan Review Notes
Plan Review Notes For Permit 22101024
Permit Number 22101024
Review Stop E
Sequence Number 1
Notes
Date Text
2022-12-07 14:50:52FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 1ST ELECTRICAL REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RUBEN PEREZ PERDOMO WITH THE FOLLOWING COMMENTS -
  
 1. THE 7TH EDITION (2020) FLORIDA BUILDING CODE IN
 EFFECT ON DECEMBER 31, 2020 INCLUDES ADOPTION OF THE
 2017 NEC (NFPA 70A). REVIEW THE GENERAL ELECTRICAL
 NOTES, NEED TO BE IN ACCORDANCE WITH THE FBC 2020 7TH
 ED.
 2. SMOKE ALARMS (SMOKE DETECTION) SYSTEM AND CO (CARBON
 MONOXIDE) DETECTION SYSTEM SHALL BE PROVIDED IN
 ACCORDANCE WITH NFPA 72, FBC 907, IRC 314, IRC 315
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 THANK YOU,
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  