| 2022-11-28 10:38:11 | 1ST NFIP PLAN REVIEW | | | FINISHED CONSTRUCTION ELEVATION CERTIFICATE: | | | CORRECTIONS REQUIRED | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | 1. ATTACH A COPY OF THE ICC-ES REPORT FOR THE SMART | | | VENTS. | | | | | | 2. LINE C2E) LOWEST ELEVATION OF MACHINERY... 7.1FT | | | NAVD. MINIMUM ELEVATION SHALL BE 8'0"NAVD. | | | | | | 3. LINE A8 SHOULD BE FILLED OUT IN PLACE OF A9 (THE | | | GARAGE IS THE BUILDING - NOT AN ATTACHED GARAGE) | | | | | | 4. LINE B9 = SHOULD BE 6 (THE BUILDING IN QUESTION IS | | | IN AE 6) | | | | | | 5. LINE C2(D) = SHOULD BE N/A ITS NOT THE ATTACHED | | | GARAGE IT IS THE BUILDING. | | | | | | 6. SECTION D = THE BOX THAT SAYS CHECK HERE IF | | | ATTACHMENTS SHOULD BE CHECKED (THE SMART VENT DOCUMENTS | | | WOULD BE THE ATTACHMENTS). | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | | | | |
|