| 2023-01-12 14:32:14 | RESIDENTIAL (R2) REVIEW COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #22100952 | | | 1801 N FLAGLER DR # 309 | | | | | | 1-FLOORING SOUND INSULATION MATERIAL: | | | | | | A) OK. | | | | | | ORIGINAL COMMENT: | | | B) PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC) | | | TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY | | | SEC. 1207.2 OF FBC 7TH EDITION (2020). | | | | | | RESPONSE: | | | TEST SUBMITTED IS FOR LAMINATED WOOD OVER LV200 | | | UNDERLAYMENT. NEED TEST FOR LUXURY VINYL PLANK NOT FOR | | | LAMINATED WOOD. | | | | | | ORIGINAL COMMENT: | | | C) PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC) | | | TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY | | | SEC. 1207.3 OF FBC 7TH EDITION (2020). | | | | | | RESPONSE: | | | TEST SUBMITTED IS FOR LAMINATED WOOD OVER LV200 | | | UNDERLAYMENT. NEED TEST FOR LUXURY VINYL PLANK NOT FOR | | | LAMINATED WOOD. | | | | | | NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING | | | CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE | | | TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT | | | ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED | | | ACOUSTICAL CEILINGS IN THESE BUILDINGS. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | | | | |
|