| 2022-12-27 13:54:18 | RESIDENTIAL (R2) BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #22100952 |
| | 1801 N FLAGLER DR # 309 |
| | |
| | 1-FLOORING SOUND INSULATION MATERIAL: |
| | A) PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE |
| | DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 7TH EDITION |
| | (2020). |
| | |
| | B) PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC) |
| | TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY |
| | SEC. 1207.2 OF FBC 7TH EDITION (2020). |
| | |
| | C) PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC) |
| | TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY |
| | SEC. 1207.3 OF FBC 7TH EDITION (2020). |
| | |
| | NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING |
| | CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE |
| | TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT |
| | ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED |
| | ACOUSTICAL CEILINGS IN THESE BUILDINGS. |
| | |
| | 2- VALUATION: |
| | VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT AS REQUIRED BY SEC. |
| | 109.3 CITY AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL |
| | COSTS. PROVIDE COMPLETE COST BREAKDOWN. |
| | |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |