| 2022-12-09 13:37:59 | ELECTRIC REVIEW FAILED |
| | 1) PLEASE PROVIDE A LOAD CALCULATION FOR THE EXISTING |
| | SUB PANEL. NEC 215.5 AND NEC 555.12 |
| | 2) PLEASE INDICATE GFI PROTECTION FOR DOCK FEEDERS AS |
| | REQUIRED BY NEC 555.3 |
| | 3) PLEASE PROVIDE A NOTE ON PLANS STATING ELECTRICAL |
| | CONNECTIONS WILL COMPLY WITH NEC 555.9 |
| | 4) PLEASE INDICATE SIGNAGE REQUIRED BY NEC 555.24 IS TO |
| | BE INSTALLED OR IS EXISTING |
| | 5) PLEASE PROVIDE A NOTE ON PLANS STATING FUTURE WORK |
| | IS TO BE DONE UNDER A SEPARATE PERMIT. FBC 107.2 |
| | 6) VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| | LOW. PROVIDE A BREAKDOWN OF ALL MATERIALS AND LABOR, |
| | OR, AT YOUR DISCRETION, PROVIDE A SIGNED CONTRACT OR |
| | PROVIDE A REASONABLE VALUE. WPB F.B.C. 109.3 |
| | 7) PLEASE HAVE THE DESIGNER WHO PREPARED DRAWINGS |
| | INDICATE WHO THEY ARE AND SIGN THEM. SECTION 107.2.1 |
| | WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025. |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |