| 2023-03-07 13:43:00 | 4TH REVIEW FMC |
| | PERMIT: 22100890 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) WITH THIS CHANGE OF USE GOING FROM EDUCATIONAL TO AN |
| | ASSEMBLY OCCUPANCY THE OUTDOOR AIR CALCULATIONS MUST BE |
| | SUBMITTED TO SHOW THAT THE MECHANICAL SYSTEMS CAN |
| | HANDLE THE EXTRA LOAD OF MORE PEOPLE BEING ABLE TO |
| | OCCUPY THE SAME SPACE. PLEASE SUBMIT THE REQUIRED |
| | OUTDOOR AIR CALCULATIONS FOR THIS USE OF SPACE. THE |
| | OCCUPANCY CLASSIFICATION THAT MOST CLOSELY RESEMBLES |
| | THE USE FROM TABLE 403.3.1.1 MUST BE USED FOR THE |
| | CALCULATIONS. THE OCCUPANT DENSITY FOR THIS OCCUPANCY |
| | CLASSIFICATION MUST BE USED TO FIND THE MINIMUM |
| | REQUIRED OCCUPANTS FOR THIS CALCULATION. FMC 403.3.1.1 |
| | AND TABLE 403.3.1.1. |
| | |
| | 2) THE DESIGNER MUST SHOW THAT THE MECHANICAL SYSTEMS |
| | THAT ARE EXISTING ARE SIZED CORRECTLY FOR THIS CHANGE |
| | OF USE. FEC C403.2.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |