| 2023-02-14 14:17:37 | 3RD REVIEW FMC | | | PERMIT: 22100890 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THIS CHANGE OF USE DOES REQUIRE THE SPACE TO MEET | | | THE OUTDOOR AIR REQUIREMENTS FOR THIS NEW OCCUPANCY. | | | PROVIDE THE REQUIRED OUTDOOR AIR CALCULATIONS FOR THIS | | | NEW CHANGE OF USE. THE OUTDOOR AIR CALCULATIONS SHALL | | | BE DESIGNED FROM THE OCCUPANCY CLASSIFICATION AND | | | OCCUPANT DENSITY OF FMC 403.3.1.1 AND TABLE 403.3.1.1 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|