| 2022-11-02 12:02:05 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22100890 7719 S DIXIE HWY |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. THE FLOOR PLAN WAS NOT DESIGNED BY EITHER AN |
| | ENGINEER OR ARCHITECT. CERTIFICATION BY CONTRACTOR. THE |
| | CONTRACTOR (QUALIFIER) THAT CREATED / DRAWN THE SET OF |
| | PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF |
| | THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND |
| | LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND |
| | PLANS DRAWN. WPB FBC 107.3.4.3 CERTIFICATION BY |
| | CONTRACTOR. |
| | PLEASE NOTE THAT WHEN SCANNED DRAWINGS ARE SUBMITTED |
| | WITH CONTRACTOR'S PRINTED NAME, SIGNATURE AND LICENSE |
| | NUMBER IN ACCORDANCE WITH WPB FBC 107.3.4.3, A PAPER |
| | PLAN WITH WET SIGNATURE SHALL BE PROVIDED TO THE |
| | BUILDING DEPARTMENT FOR HARD RECORD FILE PRIOR TO |
| | ISSUANCE OF A PERMIT. |
| | PER WPB FBC 107.2.1, PLEASE REFERENCE ON THE PLANS THE |
| | CODES THAT APPLY (SEE LIST ABOVE) |
| | |
| | 2. PROVIDE A FULL SCOPE OF WORK AND AS APPLICABLE, AN |
| | EXISTING/DEMOLITION PLUMBING FLOOR PLAN WITH ALL |
| | EXISTING PLUMBING FIXTURES AND EQUIPMENT INCLUDING |
| | WATER HEATERS AND A PROPOSED PLUMBING FLOOR PLAN WITH |
| | ALL PLUMBING FIXTURES AND EQUIPMENT INCLUDING WATER |
| | HEATERS. PROVIDE AS APPLICABLE, PLUMBING PLAN VIEW TO |
| | INCLUDE WATER AND SANITARY PIPING, PLUMBING FIXTURES, |
| | NEW OR EXISTING WATER SERVICE BACKFLOW PREVENTER AND |
| | EQUIPMENT INCLUDING WATER HEATERS AND PLUMBING |
| | WATER/SANITARY RISER DIAGRAMS AND DETAILS. ADDRESS AS |
| | APPLICABLE, THE REQUIREMENTS OF WPB FBC 107.3.5.1.3 |
| | BELOW. |
| | 1. MINIMUM PLUMBING FACILITIES |
| | 2. FIXTURE REQUIREMENTS |
| | 3. WATER SUPPLY PIPING |
| | 4. SANITARY DRAINAGE |
| | 5. WATER HEATERS |
| | 6. VENTS |
| | 7. ROOF DRAINAGE |
| | 8. BACKFLOW PREVENTION |
| | 9. IRRIGATION |
| | 10. LOCATION OF WATER SUPPLY LINE |
| | 11. GREASE TRAPS |
| | 12. ENVIRONMENTAL REQUIREMENTS |
| | 13. PLUMBING RISER (SANITARY AND WATER) |
| | 14. DESIGN FLOOD ELEVATION |
| | |
| | 3. PER WPB FBC 107.2.1, PLEASE PROVIDE NEW OCCUPANCY |
| | DESIGNATION AS SPELLED OUT IN FBC SECTION 302 AND |
| | PROVIDE OCCUPANCY LOAD FOR DESIGNATED CLASSIFICATION AS |
| | SPELLED OUT IN FBC SECTION 1004 SO THAT A DETERMINATION |
| | OF MINIMUM PLUMBING FIXTURE REQUIREMENTS CAN BE |
| | DETERMINED IN ACCORDANCE WITH FBC PL SECTION 403; |
| | PROVIDE PLUMBING FIXTURE SCHEDULE SHOWING MINIMUM |
| | FIXTURE REQUIREMENTS FOR THE OCCUPANCY IN ACCORDANCE |
| | WITH FBC PL TABLE 403.1 AND THE ACTUAL FIXTURES |
| | PROVIDED. |
| | |
| | 4. A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS (SEE FBC PL 404.1) BUT IS TYPICALLY ADDRESSED |
| | ON THE ARCHITECTURAL PLANS. ANY COMMENTS CONCERNING |
| | THESE REQUIREMENTS MUST BE SATISFACTORILY ADDRESSED |
| | PRIOR TO A PLUMBING REVIEW APPROVAL; PROVIDE PLAN AND |
| | ELEVATION DETAILS FOR ACCESSIBLE TOILET ROOM |
| | FACILITIES, DRINKING FOUNTAIN(S) AND ACCESSIBLE SINKS. |
| | COMPLY WITH FBC ACC CHAPTERS 2, 3 AND 6. |
| | |
| | 5. VALUE OF JOB MAY NEED TO BE ADJUSTED BASED UPON A |
| | PROPOSED SCOPE OF WORK AND RESUBMITTALS. PROVIDE AN |
| | ACCURATE VALUATION OF ALL WORK AND COST. WPB FBC 109.3 |
| | BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF THE |
| | BUILDING OFFICIAL, THE CLAIMED VALUATION OF BUILDING, |
| | ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR |
| | PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE |
| | APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE |
| | APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR |
| | BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO |
| | MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR |
| | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS |
| | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL (1) CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | |
| | END OF COMMENTS. |
| | A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT |
| | THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A |
| | RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS |
| | FROM THE FIRST REVIEW. |
| | |
| | |