| 2023-01-17 11:17:33 | PLUMBING PLAN AUDIT |
| | PERMIT- 22100869 |
| | 1/17/2023 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | AUDIT RESULTS. |
| | |
| | 1) ARCH. (A) & PLUMB. (P) SHEETS: PLEASE LABEL THE |
| | TOILET ROOMS AS EITHER MALE AND FEMALE OR UNISEX IN |
| | ACCORDANCE WITH SECS. 403.2 & 403.2.1 FBC P. PLEASE |
| | NOTE SEC. 403.3 REQUIRES THAT TOILET FACILITIES BE |
| | PROVIDED FOR BOTH THE PUBLIC AND EMPLOYEES. THE VIP |
| | BATHROOM DESIGNATION APPEARS TO IMPLY EXCLUSIVE USE |
| | WHICH IS NON-COMPLIANT. |
| | |
| | 2) ARCH. (A) & PLUMB. (P) SHEETS: THE DRINKING |
| | FOUNTAINS HAVE LEADING EDGES THAT ARE PROTRUDING INTO |
| | THE CIRCULATION PATH BEYOND THE MAXIMUM 4-INCHES |
| | ALLOWABLE- SEC. 307.2 FBC ACC. |
| | |
| | 3) A8.00- FBC ACC DEFICIENCIES: |
| | A) DETAILS 1 & 6: SHOW THE DIMENSIONS OF THE WATER |
| | CLOSET CLEAR SPACES, AND THE CLEAR FLOOR SPACE DIAGRAM |
| | AND DIMENSIONS FOR THE LAVATORIES- SECS. 604.3 & 606.2. |
| | B) DETAIL 6: SHOW THE DIAMETER OF THE TURNING CIRCLE- |
| | SEC. 304.3. |
| | C) DETAILS 1, 5, 6, & 8: SHOW THE CENTERLINES OF THE |
| | WATER CLOSET DRAINS MEASURED FROM THE ADJACENT WALLS- |
| | 604.2. |
| | D) DETAILS 1, 2, 6, & 9: THE MINIMUM WATER CLOSET GRAB |
| | LENGTHS AND MAX SPACING FROM THE SIDE WALLS ARE NOT |
| | DETAILED IN COMPLIANCE WITH SEC. & FIGURE 604.5.1. |
| | E) PROVIDE THE CLEAR FLOOR SPACE DIAGRAMS AND |
| | DIMENSIONS FOR THE BREAK ROOM AND EXAM ROOM SINKS- |
| | SECS. 212.3 & 606.2. |
| | F) PROVIDE THE HEIGHTS OF THE BREAK ROOM AND EXAM SINK |
| | RIMS OR COUNTER SURFACES FROM THE FINISHED FLOOR- SEC. |
| | 212,3 & 606.3. |
| | |
| | 4) SHEETS P0.1 & P2.1: THE ISOMETRIC DRAWINGS SHOW |
| | SKS-1, 2, & 3 WHICH ARE NOT INCLUDED IN THE FIXTURE |
| | SCHEDULE- SEC. 107.2.1 WPB. |
| | |
| | 5) P2.1: PROVIDE VENTS FOR THE SK-2 SINKS LOCATED IN |
| | THE LASER ROOM, AND BY THE BIO-HAZARD CLOSET- SEC. |
| | 902.2.1 FBC P. PLEASE NOTE THE SINKS CANNOT BE VENTED |
| | USING THE THE HORIZONTAL WET VENT FOR THE BATHROOM- |
| | SEC. 912.1. |
| | |
| | 6) P2.1: INDICATE HOW TEMPERED WATER WILL BE DELIVERED |
| | FROM THE LAVATORY SINKS- SEC. 419.5 & 607.1.2 FBC P. |
| | |
| | 7) P3.1: A MEANS OF LIMITING THE HOT WATER TEMPERATURE |
| | AT THE WATER HEATER IS REQUIRED PER SEC. 607.1.1 FBC P. |
| | PLEASE PROVIDE A MASTER THERMOSTATIC MIXING VALVE AND |
| | SHOW THE LOCATION IN THE WATER HEATER PIPING DETAIL. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |