| 2022-10-26 14:07:48 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET CS - THERE IS AN INDICATION UNDER APPLICABLE |
| | CODES OF THE 6TH ED OF NFPA 101. |
| | |
| | THE CURRENT EDITION OF NFPA 101 ADOPTED BY THE STATE OF |
| | FLORIDA IS THE 7TH ED. |
| | |
| | PLEASE REVIEW, ENSURE COMPLIANCE AND CORRECT. |
| | |
| | |
| | |
| | 1A) SHEET CS - THERE IS AN INDICATION UNDER APPLICABLE |
| | CODES OF THE NFPA 101, OF CHAPTER 42. |
| | |
| | THE CLASSIFICATION OF BUSINESS OCCUPANCY WITHIN NFPA |
| | 101 IS CHAPTER 38 |
| | |
| | PLEASE REVIEW, ENSURE COMPLIANCE AND CORRECT. |
| | |
| | |
| | 2) SHEET CS - THERE IS AN INDICATION UNDERNOTES OF |
| | INTERIOR FINISHES COMPLYING WITH LIFE SAFETY 101 2015 |
| | ED. |
| | |
| | THE CURRENT EDITION OF NFPA 101 ADOPTED BY THE STATE OF |
| | FLORIDA IS THE 2020 ED.. |
| | |
| | PLEASE REVIEW, ENSURE COMPLIANCE AND CORRECT |
| | |
| | |
| | |
| | 3) SHEET A2.00 - THERE IS AN INDICATION UNDER FLOOR |
| | NOTES # 8 OF - SEE ROOM FINISH SCHEDULES FOR ....FLOOR |
| | COVERINGS. |
| | |
| | THE FLOOR COVERINGS COULD NOT BE LOCATED. |
| | |
| | PER NFPA 101 CH 30 |
| | |
| | 30.3.3.3 INTERIOR FLOOR FINISH. |
| | 30.3.3.3.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH |
| | SECTION 10.2. |
| | 30.3.3.3.2 INTERIOR FLOOR FINISH IN EXIT ENCLOSURES AND |
| | EXIT ACCESS COR RIDORS AND SPACES NOT SEPARATED FROM |
| | THEM BY WALLS COMPLYING WITH |
| | 30.3.6 SHALL BE NOT LESS THAN CLASS II. |
| | 30.3.3.3.3 INTERIOR FLOOR FINISH SHALL COMPLY WITH |
| | 10.2.7.1 OR 10.2.7.2, |
| | AS APPLICABLE |
| | |
| | PLEASE REVIEW, ENSURE COMPLIANCE, CORRECT AND PROVIDE A |
| | NOTE OF ACKNOWLEDGMENT. |
| | |
| | |
| | 4) SHEET A2.01 - WITHIN THE LIFE SAFETY DEVICE SYMBOL |
| | LIST THERE ARE INDICATIONS OF FIRE ALARM DEVICES. |
| | |
| | THOUGH THERE ARE NO SYMBOLS WITHIN THE FLOOR PLAN, |
| | PLEASE CLARIFY IF A FIRE ALARM WILL OR WILL NOT BE |
| | INSTALLED. |
| | |
| | SHOULD A FIRE ALARM BE INSTALLED IT SHALL BE INSTALLED |
| | UNDER A SEPARATE PERMIT AND SHOP DRAWINGS. |
| | |
| | IF SO, PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT OF THIS |
| | PLAN SHEET AND THE ELECTCAL PLAN SHEET. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |