| Plan Review Notes For Permit 22100849 |
| Permit Number |
22100849 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-01-06 14:43:28 | PREVIOUS COMMENTS NOT ADDRESSED | | | VERSION ONE OF THE COVER SHEET INDICATES 60 AMP | | | ELECTRIC SERVICES ARE PRESENT AND LOAD CALCULATION | | | PROVIDED INDICATES 100 AMP SERVICES ARE REQUIRED. | | | PROVIDE AN ENTIRE BUILDING ELECTRIC RISER DIAGRAM | | | DETAILING EXISTING CONDITIONS. INCLUDE EQUIPMENT, | | | CONDUIT, CONDUCTOR AND OVERCURRENT SIZES FOR ALL | | | SERVICE WIRING. IF ANY PROPOSED CHANGES ARE TO BE MADE, | | | PROVIDE A PROPOSED BUILDING RISER DIAGRAM DETAILING ALL | | | CHANES OR MODIFICATIONS, INCLUDE ALL ITEMS DETAILED FOR | | | EXISTING RISER DIAGRAMS. NEC 215.5 AND FBC 107.2 | | | | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|