| 2022-12-05 10:56:23 | ELECTRIC REVIEW FAILED |
| | 1) SITE PLAN EQUIPMENT LAYOUT ON SHEET PVA-1 DOES NOT |
| | REFERENCE THE SAME OR ALL OF THE EQUIPMENT ON SINGLE |
| | LINE DIAGRAM. NOMENCLATURE IS DIFFERENT FROM SHEET TO |
| | SHEET. PLEASE CORRECT AS APPLICABLE. FBC 107.2 |
| | 2) ONE LINE DIAGRAM DETAILS FEEDERS FROM METER |
| | ENCLOSURE TO TWO ELECTRIC PANELS. THIS DIAGRAM DOES NOT |
| | DETAIL CONDUCTOR SIZES. PLEASE DETAIL CONDUCTOR SIZES, |
| | KEEPING IN MIND THAT THE NEC 310.15 (B)(7)(2), |
| | REDUCTION OF AMPACITY, DOES NOT APPLY AS THESE FEEDERS |
| | DO NOT SUPPLY THE ENTIRE LOAD. NEC 215.5 |
| | 3) ENSURE STORAGE BATTERY DISCONNECTS COMPLY WITH |
| | NEC480.7(D) AND 706.7(D) FOR NOTIFICATION AND MARKING |
| | OF BATTERY VOLTAGE, MAXIMUM AVAILABLE SHORT CIRCUIT |
| | FROM BATTERY SYSTEM, DATE SHORT CIRCUIT CALCULATION WAS |
| | PERFORMED |
| | 4) PLEASE ENSURE A DIRECTORY DENOTING ALL ELECTRIC |
| | POWER SOURCES AT EACH SERVICE EQUIPMENT LOCATION AND AT |
| | LOCATIONS OF ALL POWER PRODUCTION SOURCES. IN ADDITION, |
| | FOR AN ESS STAND ALONE SYSTEM, A PLAQUE AT THE EXTERIOR |
| | OF THE BUILDING INDICATING THE LOCATION OF THE |
| | DISCONNECTING MEANS AS PER NEC 706.11 (A) AND (B) |
| | 5) PLEASE PROVIDE A SEQUENCE OF OPERATIONS FOR RAPID |
| | SHUT DOWN SYSTEM, ESS STANDALONE SYSTEM AND PV CHARGING |
| | SYSTEM IF APPLICABLE. FBC 107.2 |
| | 6) PLEASE PROVIDE ALL EQUIPMENT SPECIFICATIONS. FBC |
| | 107.2 |
| | 7) PLEASE PROVIDE AN ACCURATE GARAGE FLOOR PLAN FOR ALL |
| | EQUIPMENT. INDICATE ALL REQUIRED NEC CLEARANCES. NEC |
| | 110.26 AND OTHER NEC APPLICABLE ARTICLES |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | |