| 2022-12-15 09:56:36 | 1ST REVIEW FMC | | | PERMIT: 22100754 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-1: THERE ARE 2 FLOORS ON THIS DRAWING, THEY | | | WILL NEED TO BE LABELED OR IDENTIFIED. THE THIRD FLOOR | | | SHOULD ALSO BE IDENTIFIED ON SHEET M-2. FBC 107.3.5 | | | | | | 2) PLEASE SHOW THAT THE CONDENSING UNITS ARE A MINIMUM | | | OF 10 FEET FROM THE ROOFS EDGE OR PROVIDE THE REQUIRED | | | GUARDS. FMC 304.11 | | | | | | 3) THE FULLY SEALED DOORS SHOWN ON SHEET M-1 AND M-2 | | | NEED TO BE SHOWN ON THE DOOR SCHEDULE ON SHEET A-08. | | | FBC 107.3.5 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|