| Plan Review Notes For Permit 22100754 |
| Permit Number |
22100754 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-12-16 09:37:56 | FIRE REVIEW COMMENTS: | | | | | | (1) FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS WERE | | | NOT INCLUDED ON THE MASTER PLAN. PER FAC 61G15-32.002 | | | DEFINES THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENT | | | (5) AS WELL AS THE FIRE PROTECTION SYSTEM LAYOUT | | | DOCUMENT (6). 61G15-32.003 OUTLINES THE COMMON | | | REQUIREMENTS TO ALL FIRE PROTECTIONS ENGINEERING | | | DOCUMENTS WITH 32.004 (2) (A-J) OUTLINING THE MINIMUM | | | INFORMATION TO BE PROVIDED ON FIRE PROTECTION | | | ENGINEERING DOCUMENTS FOR WATER-BASED SYSTEMS. AS | | | STATED IN THE DEFINITIONS, THE CONTRACTOR IS TO DEVELOP | | | THE LAYOUT DOCUMENTS BASED ON THE DESIGN CRITERIA | | | PROVIDED IN THE FIRE PROTECTION ENGINEERING DOCUMENTS | | | BY THE ENGINEER OF RECORD FOR THE FIRE SPRINKLER | | | SYSTEM. THE FIRE PROTECTION SYSTEM ENGINEERING | | | DOCUMENTS ARE SUBMITTED FOR THE MASTER PERMIT (BUILDING | | | PERMIT PER FBC) AND THE LAYOUT DOCUMENTS ARE SUBMITTED | | | FOR THE FIRE SPRINKLER INSTALLATION PERMIT. | | | | | | (2) SEPARATE PERMIT AND SHOP DRAWINGS ARE NEEDED FOR | | | ANY FIRE ALARM, FIRE SPRINKLER AND UNDERGROUND | | | FIRELINE. | | | | | | (3) PLAN SUBMITTAL DOES NOT INDICATE SMOKE ALARM | | | LOCATIONS. NFPA 101, 30.3.4.5 | | | | | | (4) GRAB BARS WERE NOT INDICATED IN THE BATHTUB/SHOWER. | | | NFPA 101, 30.2.1.3 | | | | | | (5) RESUBMITTALS MAY GENERATE ADDITIONAL COMMENTS OR | | | QUESTIONS. | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|