2023-06-28 13:17:17PROVIDING THE RESPONSE OF "SHOP DRAWINGS WILL BE
 SUBMITTED" OR "DEFERRED" DOES NOT MEET THE REQUIREMENTS
 OF THE FLORIDA ADMINSTRATIVE CODE.
  
 AS STATED PREVIOUSLY:
  
 FAC 61G15-32.002 DEFINES THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENT (5) AS WELL AS THE FIRE PROTECTION
 SYSTEM LAYOUT DOCUMENT (6). 61G15-32.003 OUTLINES THE
 COMMON REQUIREMENTS TO ALL FIRE PROTECTIONS ENGINEERING
 DOCUMENTS WITH 32.004 (2) (A-J) OUTLINING THE MINIMUM
 INFORMATION TO BE PROVIDED ON FIRE PROTECTION
 ENGINEERING DOCUMENTS FOR WATER BASED SYSTEMS. AS
 STATED IN THE DEFINITIONS, THE CONTRACTOR IS TO DEVELOP
 THE LAYOUT DOCUMENTS BASED ON THE DESIGN CRITERIA
 PROVIDED IN THE FIRE PROTECTION ENGINEERING DOCUMENTS
 BY THE ENGINEER OF RECORD FOR THE FIRE SPRINKLER
 SYSTEM. THE FIRE PROTECTION SYSTEM ENGINEERING
 DOCUMENTS ARE SUBMITTED FOR THE MASTER PERMIT (BUILDING
 PERMIT PER FBC) AND THE LAYOUT DOCUMENTS ARE SUBMITTED
 FOR THE FIRE SPRINKLER INSTALLATION PERMIT.
  
 EVEN IF THE EOR DEFERS TO A LOCAL QUALIFIED CONTRACTOR,
 THAT CONTRACTOR MUST SUBMIT THE REQUIRED 61G
 INFORMATION WITH THIS MASTER.
  
 PLEASE REVIEW AND SUBMIT THE REQUIRED FAC 61G
 DOCUMENTATION WITH THIS MASTER PERMIT.
  
  