| Plan Review Notes For Permit 22100752 |
| Permit Number |
22100752 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-07-05 14:15:26 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | | | 1. PROVIDE ONE-LINE DIAGRAM SHOWING INFORMATION OF | | | SERVICE EQUIPMENTS AND FEEDERS TO THE DIFFERENT PANELS | | | (SERVICE DISCONNECT, FEEDERS PROTECTIONS, GROUNDED | | | ELECTRICAL CONDUCTOR, AND MINIMUM SIZE FOR EQUIPMENT | | | GROUNDING CONDUCTORS) AS PER NEC 215. 230, 250 | | | | | | END OF COMMENTS | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | RUBEN P. PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER/ INSPECTOR | | | 561-805-6738 | | | [email protected] |
|