2023-06-27 13:18:57NEW 2 STORY R2
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE ACCESSIBLE ROUTE FOR THE RETAIL
 SPACE AT THE FAR SOUTH END FROM THE ACCESSIBLE PARKING
 SPACE TO THE BUILDING ENTRY - FBC A 208.3 PARKING
 SPACES COMPLYING WITH 502 THAT SERVE A PARTICULAR
 BUILDING OR FACILITY SHALL BE LOCATED ON THE SHORTEST
 ACCESSIBLE ROUTE FROM PARKING TO AN ENTRANCE COMPLYING
 WITH 206.4. ALL SPACES MUST BE LOCATED ON AN ACCESSIBLE
 ROUTE THAT IS AT LEAST 44 INCHES (1118 MM) WIDE AND SO
 THAT USERS ARE NOT COMPELLED TO WALK OR WHEEL BEHIND
 PARKED VEHICLES EXCEPT BEHIND HIS OR HER OWN VEHICLE.
 WHERE PARKING SERVES MORE THAN ONE ACCESSIBLE ENTRANCE,
 PARKING SPACES COMPLYING WITH 502 SHALL BE DISPERSED
 AND LOCATED ON THE SHORTEST ACCESSIBLE ROUTE TO THE
 ACCESSIBLE ENTRANCES. IF THERE ARE MULTIPLE ENTRANCES
 FOR MULTIPLE RETAIL STORES THE PARKING SPACES MUST BE
 DISPERSED TO PROVIDE PARKING AT THE NEAREST ACCESSIBLE
 ENTRANCE.
  
 2) PLEASE SHOW THE ACCESSIBLE RAMP SLOPE - FBC A 405.2
  
 3) PLEASE SHOW THE ACCESSIBLE RAMP HAND RAIL DETAILS
 FOR BOTH SIDES OF THE RAMP - FBC A 505.2
  
 4) PLEASE SHOW THE ACCESSIBLE RAMP LANDING SIZES TO
 COMPLY WITH FBC A 405.7.3LENGTH. THE LANDING CLEAR
 LENGTH SHALL BE 60 INCHES (1525 MM) LONG MINIMUM.
 FBC A 405.7.4 CHANGE IN DIRECTION. RAMPS THAT CHANGE
 DIRECTION BETWEEN RUNS AT LANDINGS SHALL HAVE A CLEAR
 LANDING 60 INCHES (1525 MM) MINIMUM BY 60 INCHES (1525
 MM) MINIMUM.
  
 5) CANNOT HAVE A CURB CUT IN A RAMP LANDING - FBC A
 405.7.1SLOPE. LANDINGS SHALL COMPLY WITH 302. CHANGES
 IN LEVEL ARE NOT PERMITTED.
  
 6) DRAWING A-4.2 AND A-6.00 DETAIL 1 SHOWS HANDRAIL
 HEIGHT AT 2' 9" - FBC 1014.2 HEIGHT. HANDRAIL HEIGHT,
 MEASURED ABOVE STAIR TREAD NOSINGS, OR FINISH SURFACE
 OF RAMP SLOPE, SHALL BE UNIFORM, NOT LESS THAN 34
 INCHES (864 MM) AND NOT MORE THAN 38 INCHES (965 MM).
  
 7) PLEASE SHOW THE CLEAR FLOOR SPACE INSIDE THE
 BATHROOMS FOR THE BATHTUBS - FBC FHA REQUIREMENT 7
  
 8) DRAWINGS SP-1, SP-2 AND THE SURVEY DO NOT SHOW AS
 DIGITALLY SIGNED IN ADOBE READER - SIGNED AND SEALED
 DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
  
  
  
  
  
  
  
  
  