Plan Review Notes
Plan Review Notes For Permit 22100752
Permit Number 22100752
Review Stop M
Sequence Number 1
Notes
Date Text
2023-05-02 08:29:531ST REVIEW FMC
 PERMIT: 221007521)1)
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MANUAL JS SUBMITTED FOR WHAT I BELIEVE TO BE
 UNIT A-2 WILL NEED TO INCLUDE THE NAME AND THE ADDRESS
 OF THE UNIT IT IS SUBMITTED FOR.
  
 2) THE PERMIT APPLICATION WILL NEED TO IDENTIFY WHICH
 BUILDING IS INCLUDED FOR THIS PERMIT.
  
 3) SHEET M-1: THE EXHAUST DUCT TERMINATIONS MUST MEET
 THE 3 FEET REQUIREMENTS FROM OPERABLE OPENINGS. FMC
 501.3.1
  
 4) SHEET M-1: UNIT B1; THE EXHAUST TERMINATION LOCATION
 CAN NOT BE ON TO THE STAIRWAY. FMC 501.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  