| Plan Review Notes For Permit 22100752 |
| Permit Number |
22100752 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-05-02 08:29:53 | 1ST REVIEW FMC | | | PERMIT: 221007521)1) | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE MANUAL JS SUBMITTED FOR WHAT I BELIEVE TO BE | | | UNIT A-2 WILL NEED TO INCLUDE THE NAME AND THE ADDRESS | | | OF THE UNIT IT IS SUBMITTED FOR. | | | | | | 2) THE PERMIT APPLICATION WILL NEED TO IDENTIFY WHICH | | | BUILDING IS INCLUDED FOR THIS PERMIT. | | | | | | 3) SHEET M-1: THE EXHAUST DUCT TERMINATIONS MUST MEET | | | THE 3 FEET REQUIREMENTS FROM OPERABLE OPENINGS. FMC | | | 501.3.1 | | | | | | 4) SHEET M-1: UNIT B1; THE EXHAUST TERMINATION LOCATION | | | CAN NOT BE ON TO THE STAIRWAY. FMC 501.3 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|