2023-04-20 11:12:14NEW 2 STORY R2
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) 2ND FLOOR NORTH END UNIT SHOWS A DOOR OPENING WITH
 OUT A BALCONY - PLEASE CLARIFY
  
 2) DRAWING A-1.0 AND LS-1 UNDER - SCOPE OF WORK - SHOWS
 (2) 3 STORY - THE DRAWINGS SHOW A 2 STORY BUILDING -
 PLEASE CLARIFY
  
 3) DRAWING LS-1 SHOWS CONSTRUCTION TYPE AS IIIA AND
 DRAWING A-1.0 SHOWS CONSTRUCTION TYPE AS IIIB - PLEASE
 CLARIFY.
  
 4) DRAWING S-2.1 AND S-2.2 SHOW A 3 STORY BUILDING -
 ALL OTHER DRAWINGS SHOW A 2 STORY BUILDING - PLEASE
 CLARIFY.
  
 5) DRAWING A-1.0 SHOWS ASCE 7-10 USED FOR THE WIND
 DESIGN - SHOULD BE ASCE 7-16 PER FBC CHAPTER 35
  
 6) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS THAT ARE LISTED ON THE DRAWINGS FOR
 THE EXTERIOR WINDOWS, DOORS AND ROOFING SYSTEMS.
  
 7) PLEASE SHOW THE ACCESSIBLE ROUTE FOR THE RETAIL
 SPACE AT THE FAR SOUTH END - FBC A 208.3 PARKING SPACES
 COMPLYING WITH 502 THAT SERVE A PARTICULAR BUILDING OR
 FACILITY SHALL BE LOCATED ON THE SHORTEST ACCESSIBLE
 ROUTE FROM PARKING TO AN ENTRANCE COMPLYING WITH 206.4.
 ALL SPACES MUST BE LOCATED ON AN ACCESSIBLE ROUTE THAT
 IS AT LEAST 44 INCHES (1118 MM) WIDE AND SO THAT USERS
 ARE NOT COMPELLED TO WALK OR WHEEL BEHIND PARKED
 VEHICLES EXCEPT BEHIND HIS OR HER OWN VEHICLE. WHERE
 PARKING SERVES MORE THAN ONE ACCESSIBLE ENTRANCE,
 PARKING SPACES COMPLYING WITH 502 SHALL BE DISPERSED
 AND LOCATED ON THE SHORTEST ACCESSIBLE ROUTE TO THE
 ACCESSIBLE ENTRANCES. IF THERE ARE MULTIPLE ENTRANCES
 FOR MULTIPLE RETAIL STORES THE PARKING SPACES MUST BE
 DISPERSED TO PROVIDE PARKING AT THE NEAREST ACCESSIBLE
 ENTRANCE.
  
 8) PLEASE SHOW BARRIERS UNDER STAIRS - FBC A 307.4
 VERTICAL CLEARANCE.
 VERTICAL CLEARANCE SHALL BE 80 INCHES (2030 MM) HIGH
 MINIMUM. GUARDRAILS OR OTHER BARRIERS SHALL BE PROVIDED
 WHERE THE VERTICAL CLEARANCE IS LESS THAN 80 INCHES
 (2030 MM) HIGH. THE LEADING EDGE OF SUCH GUARDRAIL OR
 BARRIER SHALL BE LOCATED 27 INCHES (685 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 9) PLEASE PROVIDE A SITE PLAN - CLARIFYING ALL
 ACCESSIBLE PATHWAYS - WIDTHS AND LOCATIONS - FBC A 206
  
 10) PLEASE SHOW THE CLEAR FLOOR SPACE INSIDE THE
 BATHROOMS FOR THE BATHTUBS - FBC FHA REQUIREMENT 7
  
 11) PLEASE SHOW THE GRAB BAR BACKING LOCATIONS FOR THE
 2 BEDROOM UNITS - FBC FHA REQUIREMENT 6
  
 12) FOR THE 2ND FLOOR SOUND TRANSMISSION REQUIREMENT -
 THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 13) EXTERIOR WINDOW, DOOR AND ROOFING SYSTEM PRODUCT
 APPROVALS MAY BE DEFERRED SUBMITTALS BY LISTING ITEMS
 TO BE DEFERRED ON THE CONSTRUCTION DOCUMENTS - FBC
 WPB107.3.4.1 DEFERRED SUBMITTALS.