| 2023-06-14 11:19:43 | |
| | 3RD REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22100751 |
| | 6/14/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | FHDA- FAIR HOUSING DESIGN ACT MANUAL |
| | |
| | PLAN REVIEW RESULTS: DENIED. 3RD REQUEST FOR THE |
| | POTABLE WATER BACKFLOW PERMIT APPLICATION TO BE |
| | SUBMITTED. IF YOU DON'T UNDERSTAND WHAT IS REQUIRED |
| | PLEASE CONTACT ME. |
| | |
| | 1) AS PREVIOUSLY REQUESTED, PLEASE SUBMIT THE PERMIT |
| | APPLICATION FOR THE POTABLE WATER BACKFLOW PREVENTER- |
| | THE SUBMITTED PLUMBING PLANS FOR THE BUILDING WILL NOT |
| | BE APPROVED UNTIL A PERMIT APPLICATION FOR THE POTABLE |
| | WATER BACKFLOW PREVENTER HAS BEEN SUBMITTED. YOU CAN |
| | SUBMIT AN APPLICATION TBD (TO BE DETERMINED) IF YOU DO |
| | NOT HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED |
| | PERMIT APPLICATION TO [email protected]. YOU WILL |
| | RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU |
| | MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE |
| | APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT |
| | YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER |
| | YOU HAVE THE PERMIT GENERATED, NOTIFY ME VIA EMAIL AND |
| | I WILL CHANGE THE REVIEW STATUS TO PASS. |
| | |
| | 2) SHEET A-10.1 DETAIL 2: PLEASE SHOW THE WIDTH |
| | MEASUREMENT OF THE WATER CLOSET CLEAR FLOOR SPACE AS |
| | REQUIRED BY SEC. 604.3 FBC ACC. |
| | |
| | 3) A10.0, A10.2: THE REQUIRED 30X48-INCH CLEAR FLOOR |
| | SPACE DIAGRAM FOR THE BATHTUB SHOWING A PERPENDICULAR |
| | APPROACH IN THE TYPE A BATHROOM WAS REMOVED. THIS |
| | REQUIRED CLEAR FLOOR SPACE ALSO SERVES AS THE |
| | MANEUVERABLE CLEARANCE BEYOND THE ARC OF THE INSWINGING |
| | DOOR- REFER TO EXAMPLE A BATHROOM ON PAGE 7.36 OF THE |
| | FHDA MANUAL. |
| | |
| | 4) A10.0, A10.2: PLEASE REMOVE THE ROOM DIMENSIONS FORM |
| | THE GENERIC FHDA FLOOR PLANS TO AVOID CONFLICT WITH THE |
| | DIMENSIONS SHOWN ON THE SITE SPECIFIC FLOOR PLANS- SEC. |
| | 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |