2022-12-15 08:44:571ST REVIEW FMC
 PERMIT: 22100751
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW THAT THE CONDENSING UNITS AND ROOF
 HATCH ARE A MINIMUM OF 10 FEET FROM THE ROOFS EDGE OR
 PROVIDE THE REQUIRED GUARDS. FMC 304.11
  
 2) PLEASE SHOW THAT ALL 3 BEDROOM MECHANICAL UNITS WILL
 PROVIDE THE REQUIRED 60 CFMS OF OUTDOOR AIR. FMC TABLE
 403.3.1.1
  
 3) THE FULLY SEALED DOORS SHOWN ON SHEET M-1 AND M-2
 NEED TO BE SHOWN ON THE DOOR SCHEDULE ON SHEET A-08.
 FBC 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  