| 2022-12-15 15:36:11 | NEW APT BUILDING |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS AND |
| | ROOFING SYSTEMS. ALL PRODUCT APPROVALS NEED TO BE |
| | REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER |
| | OF RECORD FBC WPB 107.3.4 |
| | |
| | 2) PLEASE SHOW THE REQUIRED GUARD RAILING NEAR THE ROOF |
| | SCUTTLE HOLE - FBC 1015.7 ROOF ACCESS. |
| | GUARDS SHALL BE PROVIDED WHERE THE ROOF HATCH OPENING |
| | IS LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR |
| | OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN |
| | SIDE IS LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE |
| | FLOOR, ROOF OR GRADE BELOW. THE GUARD SHALL BE |
| | CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21 |
| | INCHES (533 MM) IN DIAMETER. |
| | |
| | 3) PLEASE SHOW UNIT FIRE RATED DOOS TO BE SELF CLOSING |
| | - FBC 716.5.9 |
| | |
| | 4) PLEASE SHOW THE FINISH FLOORING TYPE. FOR THE UNITS |
| | ABOVE THE GROUND FLOOR THE FOLLOWING ACUSTICAL TEST |
| | REPORTS ARE REQUIRED: |
| | |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.. |
| | PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING |
| | SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY |
| | DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP |
| | CEILING DESCRIPTION) |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP |
| | CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING |
| | ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED |
| | DROP CEILING DESCRIPTION) |
| | |
| | 5) SEPARATE PERMITS ARE REQUIRED FOR - DUMPSTER |
| | ENCLOSURE, TRELLIS, PARKING LOT, SITE LIGHTING, |
| | RETAINING WALL, PLAYGROUND EQUIPMENT AND EXISTING |
| | BUILDING DEMOLITION - PLEASE ACKNOWLEDGE THIS. |
| | |
| | 6) FLOORING TEST REPORTS, WINDOW, DOOR AND ROOFING |
| | SYSTEM PRODUCT APPROVALS MAY BE DEFERRED SUBMITTALS BY |
| | LISTING ITEMS TO BE DEFERRED ON THE CONSTRUCTION |
| | DOCUMENTS - FBC WPB 107.3.4.1 |
| | |
| | 7) THE PROVIDED SURVEY DOES NOT SHOW AS DIGITALLY |
| | SIGNED IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN |
| | PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED |
| | TO BE USED IN ELECTRONIC PLAN REVIEW. (A |
| | CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED |
| | A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF |
| | E-SIGNATURE). |
| | |