| Date |
Text |
| 2023-05-02 08:27:12 | 3RD REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22100740 |
| | 5/2/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | FHDA- FAIR HOUSING DESIGN ACT MANUAL |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) AS PREVIOUSLY REQUESTED, PLEASE SUBMIT THE PERMIT |
| | APPLICATION FOR THE POTABLE WATER BACKFLOW PREVENTER- |
| | THE SUBMITTED PLUMBING PLANS FOR THE BUILDING WILL NOT |
| | BE APPROVED UNTIL A PERMIT APPLICATION FOR THE POTABLE |
| | WATER BACKFLOW PREVENTER HAS BEEN SUBMITTED. YOU CAN |
| | SUBMIT AN APPLICATION TBD (TO BE DETERMINED) IF YOU DO |
| | NOT HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED |
| | PERMIT APPLICATION TO [email protected]. YOU WILL |
| | RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU |
| | MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE |
| | APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT |
| | YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER |
| | YOU HAVE THE PERMIT GENERATED, NOTIFY ME VIA EMAIL AND |
| | I WILL CHANGE THE REVIEW STATUS TO PASS. |
| | |
| | 2) SHEETS A1.0 & A05.3: THE LOCATION OF THE ENLARGED |
| | 3-BEDROOM UNIT FLOOR PLAN ON A05.3 DOES NOT MATCH THE |
| | LOCATION SHOWN ON THE A1.0. PLEASE SHOW THE ACCESSIBLE |
| | ROUTE INTO THE ADA COMPLIANT UNIT- SECS. 206.1, |
| | 206.2.4, 206.4 FBC ACC. |
| | |
| | 3) SHEET A10.1: CORRECT CLEAR FLOOR SPACES IN DETAIL 2 |
| | TO SHOW A FORWARD APPROACH TO THE LAVATORY EXTENDING |
| | UNDER THE UNIT, AND A PARALLEL APPROACH TO THE BATHTUB |
| | IN ACCORDANCE WITH SECS. 606.2 AND 607.2 FBC. |
| | |
| | 4) A10.1: PLEASE DETAIL THE REQUIRED GRAB BAR AT THE |
| | BATHTUB HEAD END WALL- SEC. 607.4.2.3 FBC ACC. |
| | |
| | 5) P-3 & P-4: THE PVC WATER HEATER DRAIN LINES IN THE |
| | AC CLOSET PLENUM ENCLOSURES ARE NOT PERMITTED PER SEC |
| | 602.2.1 FBC M. PVC IS COMBUSTIBLE MATERIAL AND CAN BE |
| | USED OUTSIDE OF THE ENCLOSURES. PLEASE SELECT A DRAIN |
| | MATERIAL THAT MEETS COMPLIANCE SUCH AS COPPER. |
| | |
| | 5A) P-4: THE PLAN DOES NOT SHOW THE WATER HEATER DRAIN |
| | PAN LINE RUNS AND DISCHARGE LOCATIONS FOR UNITS B-3 & |
| | C-3- SECS. 504.7.1 & 504.7.2 FBC P. |
| | |
| | 6) P-5: PLEASE CORRECT THE NOTE FROM THE FBC RES. CODE |
| | INDICATING NON-RECIRCULATED HOT WATER SHALL NOT EXCEED |
| | 100 FT. REFER TO SEC. 607.2 FBC P- THE LONGEST |
| | ALLOWANBLE DISTANCE IS 50 FT. |
| | |
| | 7) P-6: A NEW WATER HEATER NOTE INDICATES A TEMPERATURE |
| | LIMITING DEVICE SHALL BE PROVIDED HOWEVER NO DEVICE IS |
| | SHOWN. PLEASE SHOW THE LOCATION OF THE DEVICE AND |
| | PIPING CONNECTIONS- SEC. 607.1.1 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |