Plan Review Notes
Plan Review Notes For Permit 22100740
Permit Number 22100740
Review Stop P
Sequence Number 3
Notes
Date Text
2023-05-02 08:27:123RD REVIEW FBC-2020 PLUMBING
 PERMIT- 22100740
 5/2/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 FHDA- FAIR HOUSING DESIGN ACT MANUAL
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AS PREVIOUSLY REQUESTED, PLEASE SUBMIT THE PERMIT
 APPLICATION FOR THE POTABLE WATER BACKFLOW PREVENTER-
 THE SUBMITTED PLUMBING PLANS FOR THE BUILDING WILL NOT
 BE APPROVED UNTIL A PERMIT APPLICATION FOR THE POTABLE
 WATER BACKFLOW PREVENTER HAS BEEN SUBMITTED. YOU CAN
 SUBMIT AN APPLICATION TBD (TO BE DETERMINED) IF YOU DO
 NOT HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED
 PERMIT APPLICATION TO [email protected]. YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT GENERATED, NOTIFY ME VIA EMAIL AND
 I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 2) SHEETS A1.0 & A05.3: THE LOCATION OF THE ENLARGED
 3-BEDROOM UNIT FLOOR PLAN ON A05.3 DOES NOT MATCH THE
 LOCATION SHOWN ON THE A1.0. PLEASE SHOW THE ACCESSIBLE
 ROUTE INTO THE ADA COMPLIANT UNIT- SECS. 206.1,
 206.2.4, 206.4 FBC ACC.
  
 3) SHEET A10.1: CORRECT CLEAR FLOOR SPACES IN DETAIL 2
 TO SHOW A FORWARD APPROACH TO THE LAVATORY EXTENDING
 UNDER THE UNIT, AND A PARALLEL APPROACH TO THE BATHTUB
 IN ACCORDANCE WITH SECS. 606.2 AND 607.2 FBC.
  
 4) A10.1: PLEASE DETAIL THE REQUIRED GRAB BAR AT THE
 BATHTUB HEAD END WALL- SEC. 607.4.2.3 FBC ACC.
  
 5) P-3 & P-4: THE PVC WATER HEATER DRAIN LINES IN THE
 AC CLOSET PLENUM ENCLOSURES ARE NOT PERMITTED PER SEC
 602.2.1 FBC M. PVC IS COMBUSTIBLE MATERIAL AND CAN BE
 USED OUTSIDE OF THE ENCLOSURES. PLEASE SELECT A DRAIN
 MATERIAL THAT MEETS COMPLIANCE SUCH AS COPPER.
  
 5A) P-4: THE PLAN DOES NOT SHOW THE WATER HEATER DRAIN
 PAN LINE RUNS AND DISCHARGE LOCATIONS FOR UNITS B-3 &
 C-3- SECS. 504.7.1 & 504.7.2 FBC P.
  
 6) P-5: PLEASE CORRECT THE NOTE FROM THE FBC RES. CODE
 INDICATING NON-RECIRCULATED HOT WATER SHALL NOT EXCEED
 100 FT. REFER TO SEC. 607.2 FBC P- THE LONGEST
 ALLOWANBLE DISTANCE IS 50 FT.
  
 7) P-6: A NEW WATER HEATER NOTE INDICATES A TEMPERATURE
 LIMITING DEVICE SHALL BE PROVIDED HOWEVER NO DEVICE IS
 SHOWN. PLEASE SHOW THE LOCATION OF THE DEVICE AND
 PIPING CONNECTIONS- SEC. 607.1.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER