| 2023-01-18 13:37:13 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | FHA=FAIR HOUSING ACT DESIGN MANUAL |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22100740 2212 N TAMARIND AVE |
| | |
| | A SEPARATE PERMIT FOR THE BACKFLOW PREVENTER IS |
| | REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE |
| | PRIMARY PERMIT (AS APPLICABLE). YOU CAN SUBMIT AN |
| | APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE |
| | A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT |
| | APPLICATION TO [email protected] . YOU WILL |
| | RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU |
| | MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE |
| | APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT |
| | YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. A |
| | SEPARATE PERMIT IS REQUIRED HOWEVER A REVIEW OF THE |
| | SYSTEM UNDER THE MAIN PERMIT IS ALSO REQUIRED. |
| | AFTER YOU HAVE THE PERMIT GENERATED, PLEASE NOTIFY ME |
| | AT [email protected] AND CC SAMANTHA HILL, CHIEF PLANS |
| | EXAMINER AT [email protected] AND RYAN BROWN, CHIEF |
| | PLUMBING INSPECTOR AT [email protected] VIA EMAIL WITH |
| | THE PERMIT NUMBER. |
| | |
| | |
| | 1. A01: OCCUPANCY IS NOTED AS MIXED USE-COMMERCIAL/R-2 |
| | RESIDENTIAL. BUILDING "A" FIRST FLOOR NOTES ONE (1) 3 |
| | BEDROOM APARTMENT AND RETAIL WITH 1,144 SQ. FT. FBC |
| | 303.4 SHOWS THIS SPACE AS ASSEMBLY GROUP A-3 GYMNASIUM. |
| | PLEASE PROVIDE OCCUPANT LOAD AND MINIMUM PLUMBING |
| | FIXTURES AS WOULD BE REQUIRED IN ACCORDANCE WITH FBC PL |
| | 403.1 AND TABLE 403.1 FOR THIS SPACE. INCLUDE ANY |
| | ACCESSIBILITY REQUIREMENTS IN ACCORDANCE WITH FBC ACC |
| | CHAPTERS 2, 3 AND 6. |
| | |
| | |
| | 2. PLAN SHEET A10 BATHROOM: SPECIFY AND PROVIDE WALL |
| | REINFORCEMENT FOR GRAB BARS IN THE BATHROOMS FOR WATER |
| | CLOSET AND BATHTUB; COMPLY WITH FHA CHAPTERS 6 AND 7B. |
| | |
| | |
| | 3. PLAN SHEET P05/GENERAL PLUMBING NOTES: NOTE CALLS |
| | FOR ADDING A RECIRCULATING PUMP TO WATER HEATER. |
| | DRAWINGS DO NOT INDICATE RECIRCULATED HOT WATER. PLEASE |
| | CLARIFY. IF RECIRCULATING SYSTEMS ARE REQUIRED, PROVIDE |
| | PLANS, PUMP SPECIFICATION/SCHEDULE AND DETAIL. |
| | |
| | |
| | 4.PLAN SHEET P06/WATER HEATER DETAIL/WATER HEATER |
| | NOTES: |
| | ***A) NOTE AT DETAIL INDICATES T&P RELIEF VALVE |
| | DISCHARGE TO THE EMERGENCY PAN; PAN DRAIN TO EXTERIOR |
| | TERMINATING MINIMUM 12 INCHES FROM BUILDING. PLEASE |
| | CLARIFY; WILL THIS BE A DEDICATED LINE TO POINT OF |
| | TERMINATION OR CONNECT TO A COMMON DRAIN DISCHARGING TO |
| | POINT OF TERMINATION. PLEASE NOTE AND SHOW ROUTING AND |
| | SIZE ON PLAN. |
| | ***B) NOTE REQUIRES TEMPERATURE LIMITING DEVICE |
| | CONFORMING TO ASSE 1070 AT ALL LAVATORIES AND HAND |
| | SINKS. FBC RES AND FBC PL CODES DO NOT REQUIRE THIS |
| | (SEE FBC PL 419.5). HOWEVER, PER FBC RES P2601.1 AND |
| | FBC PL 607.1.1, 613.1, A TEMPERATURE-ACTUATED MIXING |
| | VALVE COMPLYING WITH ASSE 1017 IS REQUIRED AT THE WATER |
| | HEATER. |
| | |
| | |
| | 5. PLEASE PROVIDE A PLUMBING FIXTURE SCHEDULE AND A |
| | WATER HEATER EQUIPMENT SCHEDULE ON THE PLUMBING PLANS. |
| | FBC RES P2601.1, WPB FBC 107.2.1, WPB FBC |
| | 107.3.5.1.3(2)(5), FBC PL CHAPTER 4, CHAPTER 5. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | PLUMBING INSPECTOR BN2148 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |
| | |