| 2023-01-18 09:39:42 | 1ST REVIEW FMC | | | PERMIT: 22100740 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-1 AND AC CALCULATIONS GYM: PLEASE CORRECT | | | THE O/A CALCULATIONS FOR THE GYM THE RA RATE SHOULD BE | | | CALCULATED AT .18 AND NOT .06. OCCUPANCY CLASSIFICATION | | | IS GYM, STADIUM, ARENA PLAY AREA. FMC TABLE 403.3.1.1 | | | | | | 2) SHEET M-1: PLEASE SHOW THAT THE OUTDOOR AIR INTAKE | | | TERMINATION LOCATIONS SHALL MEET THE REQUIREMENTS OF | | | FMC 401.4. | | | | | | 3) SHEET M-2: PROVIDE DETAILS FOR THE GUARD PROTECTION | | | REQUIRED FOR THE EQUIPMENT ON THE ROOF. FMC 304.11 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|