| 2023-01-23 09:56:03 | NEW 3 STORY MULTI FAMILY |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS AND |
| | ROOFING SYSTEMS AS LISTED ON THE DRAWINGS. |
| | |
| | 2) SOME DRAWINGS SUCH AS A-1.0A AND LS-1 SHOW ASCE 7-10 |
| | USED FOR WIND DESIGN - SHOULD BE ASCE 7-16 |
| | |
| | 3) PLEASE SHOW THE GUARD AT THE ROOF HATCH - FBC 1015.7 |
| | ROOF ACCESS. |
| | GUARDS SHALL BE PROVIDED WHERE THE ROOF HATCH OPENING |
| | IS LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR |
| | OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN |
| | SIDE IS LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE |
| | FLOOR, ROOF OR GRADE BELOW |
| | |
| | 4) FIRE RATED ENTRY DOOS NEED TO SHOW THAT SELF CLOSING |
| | AND LATCHING IS REQUIRED - FBC 716.5.9 DOOR CLOSING. |
| | FIRE DOORS SHALL BE LATCHING AND SELF- OR |
| | AUTOMATIC-CLOSING IN ACCORDANCE WITH THIS SECTION. |
| | |
| | 5) PLEASE SHOW THE STAIR HANDRAIL EXTENSIONS AT THE |
| | BOTTOM TO SLOPE PER FBC 1014.6 HANDRAIL EXTENSIONS. |
| | HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING |
| | SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN |
| | ADJACENT FLIGHT OF STAIRS OR RAMP RUN. WHERE HANDRAILS |
| | ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL |
| | EXTEND HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM) |
| | BEYOND THE TOP RISER AND CONTINUE TO SLOPE FOR THE |
| | DEPTH OF ONE TREAD BEYOND THE BOTTOM RISER. |
| | |
| | 6) THE WALK IN CLOSET DOOR IN THE MASTER BED ROOM |
| | REQUIRES A 32 INCH CLEAR OPENING - FBC FHA REQUIREMENT |
| | 3 (2) |
| | |
| | 7) PLEASE PROVIDE THE FOLLOWING ACUSTICAL TEST REPORTS |
| | FOR THE UNIT FLOORING - - THE FOLLOWING ACOUSTICAL TEST |
| | REPORTS ARE REQUIRED: |
| | |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.. |
| | PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING |
| | SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY |
| | DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP |
| | CEILING DESCRIPTION) |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP |
| | CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING |
| | ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED |
| | DROP CEILING DESCRIPTION) |
| | |
| | 8) SEPARATE PERMITS ARE REQUIRED FOR - DUMPSTER |
| | ENCLOSURE, RETAINING WALL, BARBEQUE HUT, PARKING LOT. |
| | |
| | 9) ITEMS SUCH AS FLOORING ACOUSTICAL TEST REPORTS, |
| | WINDOW/DOOR/ROOFING SYSTEM PRODUCT APPROVALS MAY BE |
| | DEFERRED SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON |
| | THE CONSTRUCTION DOCUMENTS - FBC WPB 107.3.4.1 |
| | |
| | |