Plan Review Notes
Plan Review Notes For Permit 22100740
Permit Number 22100740
Review Stop B
Sequence Number 1
Notes
Date Text
2023-01-23 09:56:03NEW 3 STORY MULTI FAMILY
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS AND
 ROOFING SYSTEMS AS LISTED ON THE DRAWINGS.
  
 2) SOME DRAWINGS SUCH AS A-1.0A AND LS-1 SHOW ASCE 7-10
 USED FOR WIND DESIGN - SHOULD BE ASCE 7-16
  
 3) PLEASE SHOW THE GUARD AT THE ROOF HATCH - FBC 1015.7
 ROOF ACCESS.
 GUARDS SHALL BE PROVIDED WHERE THE ROOF HATCH OPENING
 IS LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR
 OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN
 SIDE IS LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE
 FLOOR, ROOF OR GRADE BELOW
  
 4) FIRE RATED ENTRY DOOS NEED TO SHOW THAT SELF CLOSING
 AND LATCHING IS REQUIRED - FBC 716.5.9 DOOR CLOSING.
 FIRE DOORS SHALL BE LATCHING AND SELF- OR
 AUTOMATIC-CLOSING IN ACCORDANCE WITH THIS SECTION.
  
 5) PLEASE SHOW THE STAIR HANDRAIL EXTENSIONS AT THE
 BOTTOM TO SLOPE PER FBC 1014.6 HANDRAIL EXTENSIONS.
 HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING
 SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT FLIGHT OF STAIRS OR RAMP RUN. WHERE HANDRAILS
 ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL
 EXTEND HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM)
 BEYOND THE TOP RISER AND CONTINUE TO SLOPE FOR THE
 DEPTH OF ONE TREAD BEYOND THE BOTTOM RISER.
  
 6) THE WALK IN CLOSET DOOR IN THE MASTER BED ROOM
 REQUIRES A 32 INCH CLEAR OPENING - FBC FHA REQUIREMENT
 3 (2)
  
 7) PLEASE PROVIDE THE FOLLOWING ACUSTICAL TEST REPORTS
 FOR THE UNIT FLOORING - - THE FOLLOWING ACOUSTICAL TEST
 REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 8) SEPARATE PERMITS ARE REQUIRED FOR - DUMPSTER
 ENCLOSURE, RETAINING WALL, BARBEQUE HUT, PARKING LOT.
  
 9) ITEMS SUCH AS FLOORING ACOUSTICAL TEST REPORTS,
 WINDOW/DOOR/ROOFING SYSTEM PRODUCT APPROVALS MAY BE
 DEFERRED SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON
 THE CONSTRUCTION DOCUMENTS - FBC WPB 107.3.4.1
  
  