| Notes |
| Date |
Text |
| 2022-11-28 13:31:12 | SHEET M-2: OUTDOOR AIR CALCULATIONS FOR THIS WAREHOUSE | | | SHOULD BE CALCULATED WITH 10 CFM/PERSON. | | | 17 PEOPLE X 10 = 170 + 8018 X .06 = 481 | | | 170 + 481 = 651 CFM'S OUTDOOR AIR REQUIRED FOR THIS | | | WAREHOUSE. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|