Plan Review Notes
Plan Review Notes For Permit 22100692
Permit Number 22100692
Review Stop M
Sequence Number 1
Notes
Date Text
2022-11-08 08:11:29THE REQUIRED OUTDOOR AIR FOR THESE 2 AHU'S WILL NEED TO
 MEET THE REQUIREMENTS OF FMC 405.1 FOR AIR
 CONDITIONING.
 DEFINITION OF VENTILATION AIR- THAT PORTION OF SUPPLY
 AIR THAT COMES FROM THE OUTSIDE (OUTDOORS), PLUS ANY
 RECIRCULATED AIR THAT HAS BEEN TREATED TO MAINTAIN THE
 DESIRED QUALITY OF AIR WITHIN A
 DESIGNATED SPACE.
  
 FMC 405.1: AIR-CONDITIONING SYSTEMS THAT SUPPLY
 REQUIRED VENTILATION AIR SHALL BE PROVIDED WITH
 CONTROLS DESIGNED TO AUTOMATICALLY MAINTAIN THE
 REQUIRED OUTDOOR AIR SUPPLY RATE DURING OCCUPANCY.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  