| 2022-10-25 14:16:51 | 1ST REVIEW FBC-2020 FUEL GAS | | | PERMIT- 22100670 | | | 10/25/22 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) P1 GAS RISER: TO HELP EXPEDITE THE REVIEW PLEASE | | | SHOW THE LENGTHS OF THE BRANCH PIPES AND THE TOTAL | | | DEVELOPED LENGTH OF THE PIPING- SEC. G2413.4.1 FBC RES. | | | | | | 2) P1 GAS RISER: BASED ON THE SUBMITTED SPECIFICATIONS | | | PLEASE CORRECT THE GAS LOAD OF THE RANGE TO 99,000 | | | BTU???S- SEC. G2413.2 FBC RES. | | | | | | 3) P1: INDICATE HOW COMBUSTION AIR WILL BE PROVIDED TO | | | THE RANGE AND PROVIDE CALCULATIONS- SECTION G2407.1 FBC | | | RES. | | | | | | 4) P1: THE 100,000 BTU GAS LOADS FOR THE WATER HEATERS | | | SEEM LOW. PLEASE SUBMIT MANUFACTURER???S SPECIFICATIONS | | | FOR THE UNITS TO VERIFY GAS LOADS ARE ACCURATE- SEC. | | | G2448.1 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|