| 2022-11-02 09:54:39 | ELECTRIC REVIEW FAILED |
| | 1) RISER DIAGRAM DETAILS 2/0 CU CONDUCTORS FEEDING (2) |
| | 2OO AMP PANELS IN GARAGE. |
| | RISER DIAGRAM DETAILS REDUCED CONDUCTOR AMPACITY. THE |
| | REDUCED CONDUCTOR AMPACITY IS ONLY APPLICABLE TO |
| | CONDUCTORS SERVING THE ENTIRE LOAD ASSOCIATED WITH A |
| | DWELLING. PLEASE CORRECT CONDUCTOR SIZES AS APPLICABLE. |
| | NEC 310.15 (B)(7)(2) |
| | 2) GYM IS FED BY MULTIPLES CIRCUITS FED FROM ELECTRIC |
| | PANEL IN GARAGE. THIS DOES NOT COMPLY WITH 225.30 |
| | NUMBER OF SUPPLIES. A BUILDING OR OTHER STRUCTURE THAT |
| | IS SERVED BY A BRANCH CIRCUIT OR FEEDER ON THE LOAD |
| | SIDE OF A SERVICE DISCONNECTING MEANS SHALL BE SUPPLIED |
| | BY ONLY ONE FEEDER OR |
| | BRANCH CIRCUIT. PLEASE CORRECT AS APPLICABLE. IF A |
| | SEPARATE PANEL IS TO BE INSTALLED AT THE GYM, PLEASE |
| | DETAIL IT IN THE RISER DIAGRAM AND THE REQUIRED, |
| | ADDITIONAL, GROUNDING ELECTRODE SYSTEM AS PER 250.32 |
| | 3) PLEASE CORRECT COMPRESSOR 1 AND 2, CONDUCTOR OR |
| | OVERCURRENT PROTECTION SIZES, ON PANEL SCHEDULES, TO |
| | COMPLY WITH NEC 240.4 OR 310.15 |
| | 4) PLEASE CORRECT BATHROOM GFI, CONDUCTOR, OVERCURRENT |
| | PROTECTION SIZE AND CIRCUITRY DETAILS ON PANEL |
| | SCHEDULES AND FLOOR PLANS TO COMPLY WITH NEC 210.11 |
| | (C)(3) |
| | 5) PLEASE DETAIL A NOTE ON ELECTRICAL PLANS AND COVER |
| | SHEET, STATING POOL AND GENERATOR WIRING, IF APPLICABLE |
| | REQUIRE SEPARATE PERMITS. |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |