Plan Review Notes
Plan Review Notes For Permit 22100661
Permit Number 22100661
Review Stop E
Sequence Number 2
Notes
Date Text
2022-12-01 15:12:53FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 APPOVED WITH NOTES:
  
 PERMANENTLY INSTALLED POOLS MUST COMPLY WITH NEC
 ARTICLE 680 PARTS I AND II
  
 ELECTRICAL EQUIPMENT INSTALLED IN THE WATER, WALLS, OR
 DECKS OF POOL MUST BE LISTED IN ACCORDANCE WITH NEC
 680.4 ??? APPROVAL OF EQUIPMENT
  
 MAINTENANCE DISCONNECTING MEANS MUST BE PROVIDED AND
 COMPLY WITH NEC 680.13
  
 AT LEAST ONE 15A OR 20A, 125V RECEPTACLE MUST BE
 LOCATED NOT LESS THAN 6 FT AND NOT MORE THAN 20 FT FROM
 THE INSIDE WALL OF A PERMANENTLY INSTALLED POOL PER NEC
 680.22
  
 WORKING SPACE MUST BE IN ACCORDANCE WITH NEC TABLE
 110.26(A) OR IRC E3405.2
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  