Plan Review Notes
Plan Review Notes For Permit 22100627
Permit Number 22100627
Review Stop B
Sequence Number 1
Notes
Date Text
2022-10-20 14:42:261ST ROOFING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
  
 1. REFERENCE NOA 18-0919.07 FOR THE FOLLOWING COMMENT:
 SYSTEM SELECTED-E (3).
 BASE SHEET OPTION: MECHANICAL FASTENERS
 GENERAL LIMITATIONS #7 SHALL APPLY.
 PROVIDE ENHANCED FASTENER CALCULATIONS FOR PERIMETER
 AND CORNER AREAS.
 CALCULATIONS SHALL BE PREPARED, SIGNED AND SEALED BY A
 FLORIDA PROFESSIONAL ENGINEER, REGISTERED ARCHITECT OR
 REGISTERD ROOF CONSULTANT.
  
 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE
 WITH SECTIONS107.2.1 THROUGH 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  