| 2022-11-03 13:37:53 | 2ND REVIEW FMC |
| | PERMIT: 22100618 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE OUTDOOR AIR CALCULATIONS SUBMITTED ARE |
| | INCOMPLETE AS I DO NOT SEE THE TOTAL OCCUPANTS FOR THE |
| | SPACES. IT APPEARS THAT THIS IS THE MISSING PART OF THE |
| | PUZZLE. IF THE CALCULATIONS ARE USING THE ARCHITECT???S |
| | EGRESS OCCUPANT NUMBERS INSTEAD OF FMC TABLE 403.3.1.1 |
| | TO FIND THE OCCUPANT LOAD FOR EACH SPACE THE OUTDOOR |
| | AIR NUMBERS WOULD BE LOW. THIS IS THE CASE IN THE |
| | SUBMITTED OUTDOOR AIR CALCULATIONS. PLEASE SEE BELOW |
| | THE REQUIRED MINIMUM OUTDOOR AIR FOR EACH SPACE, |
| | ACCORDING TO THE USE OF SPACE GIVEN AND THE SQUARE |
| | FOOTAGE OF EACH SPACE. PLEASE CORRECT THE OUTDOOR AIR |
| | TABLE SUBMITTED. |
| | |
| | THE CONFERENCE ROOM HAS A SQ. FOOTAGE OF 341. THIS AREA |
| | WOULD HAVE AN OCCUPANT COUNT OF 18, THIS WOULD REQUIRE |
| | 111 CFM???S OF OUTDOOR AIR. |
| | |
| | THE OFFICE SPACE HAS A SQ. FOOTAGE OF 1455. THIS AREA |
| | WOULD HAVE AN OCCUPANT COUNT OF 8, THIS WOULD REQUIRE |
| | 127 CFM???S OF OUTDOOR AIR. |
| | |
| | THE RECEPTION AREA HAS A SQ. FOOTAGE OF 304. THIS AREA |
| | WOULD HAVE AN OCCUPANT COUNT OF 10, THIS WOULD REQUIRE |
| | 68 CFM???S OF OUTDOOR AIR. |
| | |
| | THE CORRIDOR IS REQUIRED TO HAVE 19 CFM???S OF OUTDOOR |
| | AIR AND THAT CALCULATION IS CORRECT. |
| | |
| | THE STORAGE ROOM HAS A SQ. FOOTAGE OF 136. THIS AREA |
| | OUTDOOR AIRFLOW RATE IN THE BREATHING ZONE SHOULD BE |
| | CALCULATED USING .12 AND NOT .06. THIS AREA WOULD BE |
| | REQUIRED TO HAVE 16CFM???S OF OUTDOOR AIR. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |