2023-05-30 17:40:40ROOFING THIRD BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22100607
 415 31ST ST
  
  
 NOTE: A SEPARATE SUB-PERMIT IS REQUIRED FOR ROOF TO
 WALL CONNECTIONS. THIS WORK CAN NOT BE DONE BY THE
 ROOFING CONTRACTOR UNLESS ROOFING CONTRACTOR POSSESSES
 THE PROPER LICENSE TO PERFORM THIS WORK.
  
  
 PREVIOUS COMMENT FROM PRIOR PLAN REVIEWER:
 1. FBC EB 706.8. SHOW THAT THE VALUE OF THE STRUCTURE
 IS LESS THAN $300,000.00 OR SPECIFY HOW THE ROOF TO
 WALL CONNECTIONS WILL BE IMPROVED/REVISED SUBMITTED
 ENGINEER'S STRUCTURAL INVESTIGATION LETTER TO PROVIDE
 EXISTING ROOF-TO-WALL LOAD PATH CONNECTION ANALYSIS
 SHOWING COMPLIANCE WITH WIND LOADS IN TABLE 706.8.1 &
 VALIDATED BY A LICENSED FLORIDA DESIGN PROFESSIONAL.
 SECOND REQUEST.
  
 RESPOSNE:
 ENGINEER'S LETTER SUBMITTED IS FOR "STRUCTURAL
 INVESTIGATION OF EXISTING SHINGLE ROOF SYSTEM TO BE
 REPLACED WITH ASPHALTIC SHINGLE AT THE RESIDENCE BELOW
 415 31ST STREET, WEST PALM BEACH, FLORIDA 33404".
  
 A) THE ENGINEER REPORT DOESN'T PROVIDE THE REQUESTED
 INFORMATION FOR THE ROOF TO WALL CONNECTIONS. THE ROOF
 TO WALL CONNECTIONS SHALL BE IMPROVED AS REQUIRED BY
 SEC. 706.8 FBC-EXISTING BUILDING. ENGINEER TO READ SEC.
 706.8 FBC-EXISTING BUILDING AND PROVIDE REQUIRED
 INFORMATION. SPECIFY STRAPS AS REQUIRED.
 NOTE: BUILDING WAS BUILT IN 1926. ROOF TO WALL
 CONNECTIONS NEED TO MEET OR EXCEED CURRENT CODE
 STANDARDS.
  
 B) THE ADDRESS SPECIFIED ON THE ENGINEER'S LETTER IS
 INCORRECT. THE CORRECT ZIP CODE IS 33407 NOT 33404.
 REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 C)ENGINEER'S DIGITAL SIGNATURE COMMENTS:
 (1) REPORT SUBMITTED HAVE AN ENGINEER'S SELF CERTIFIED
 DIGITAL SIGNATURE. ENGINEER CAN NOT SELF CERTIFY THE
 DIGITAL SIGNATURE. THIRD PARTY CERTIFICATION IS
 REQUIRED BY FAC 61G15-23.004. (NOTE: ENGINEER TO
 CONTACT THE BOARD OF ENGINEER'S FOR SELF CERTIFIED
 DIGITAL SIGNATURE QUESTIONS).
 NOTE: PLEASE UPLOAD DRAWINGS TO PROJECTDOX WITH
 VERIFIABLE DIGITAL SIGNATURE.
  
 (2) ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH
 THE REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH
 THE TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY
 FBPE.
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/... AND REVISE DIGITAL SIGNATURE AS REQUIRED.
  
 SEC. 61G15-23.004 F.A.C. . PROCEDURES FOR DIGITALLY
 SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,