| 2023-05-30 17:40:40 | ROOFING THIRD BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #22100607 |
| | 415 31ST ST |
| | |
| | |
| | NOTE: A SEPARATE SUB-PERMIT IS REQUIRED FOR ROOF TO |
| | WALL CONNECTIONS. THIS WORK CAN NOT BE DONE BY THE |
| | ROOFING CONTRACTOR UNLESS ROOFING CONTRACTOR POSSESSES |
| | THE PROPER LICENSE TO PERFORM THIS WORK. |
| | |
| | |
| | PREVIOUS COMMENT FROM PRIOR PLAN REVIEWER: |
| | 1. FBC EB 706.8. SHOW THAT THE VALUE OF THE STRUCTURE |
| | IS LESS THAN $300,000.00 OR SPECIFY HOW THE ROOF TO |
| | WALL CONNECTIONS WILL BE IMPROVED/REVISED SUBMITTED |
| | ENGINEER'S STRUCTURAL INVESTIGATION LETTER TO PROVIDE |
| | EXISTING ROOF-TO-WALL LOAD PATH CONNECTION ANALYSIS |
| | SHOWING COMPLIANCE WITH WIND LOADS IN TABLE 706.8.1 & |
| | VALIDATED BY A LICENSED FLORIDA DESIGN PROFESSIONAL. |
| | SECOND REQUEST. |
| | |
| | RESPOSNE: |
| | ENGINEER'S LETTER SUBMITTED IS FOR "STRUCTURAL |
| | INVESTIGATION OF EXISTING SHINGLE ROOF SYSTEM TO BE |
| | REPLACED WITH ASPHALTIC SHINGLE AT THE RESIDENCE BELOW |
| | 415 31ST STREET, WEST PALM BEACH, FLORIDA 33404". |
| | |
| | A) THE ENGINEER REPORT DOESN'T PROVIDE THE REQUESTED |
| | INFORMATION FOR THE ROOF TO WALL CONNECTIONS. THE ROOF |
| | TO WALL CONNECTIONS SHALL BE IMPROVED AS REQUIRED BY |
| | SEC. 706.8 FBC-EXISTING BUILDING. ENGINEER TO READ SEC. |
| | 706.8 FBC-EXISTING BUILDING AND PROVIDE REQUIRED |
| | INFORMATION. SPECIFY STRAPS AS REQUIRED. |
| | NOTE: BUILDING WAS BUILT IN 1926. ROOF TO WALL |
| | CONNECTIONS NEED TO MEET OR EXCEED CURRENT CODE |
| | STANDARDS. |
| | |
| | B) THE ADDRESS SPECIFIED ON THE ENGINEER'S LETTER IS |
| | INCORRECT. THE CORRECT ZIP CODE IS 33407 NOT 33404. |
| | REVISE AS REQUIRED. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | C)ENGINEER'S DIGITAL SIGNATURE COMMENTS: |
| | (1) REPORT SUBMITTED HAVE AN ENGINEER'S SELF CERTIFIED |
| | DIGITAL SIGNATURE. ENGINEER CAN NOT SELF CERTIFY THE |
| | DIGITAL SIGNATURE. THIRD PARTY CERTIFICATION IS |
| | REQUIRED BY FAC 61G15-23.004. (NOTE: ENGINEER TO |
| | CONTACT THE BOARD OF ENGINEER'S FOR SELF CERTIFIED |
| | DIGITAL SIGNATURE QUESTIONS). |
| | NOTE: PLEASE UPLOAD DRAWINGS TO PROJECTDOX WITH |
| | VERIFIABLE DIGITAL SIGNATURE. |
| | |
| | (2) ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH |
| | THE REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH |
| | THE TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY |
| | FBPE. |
| | SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU |
| | MENTS/... AND REVISE DIGITAL SIGNATURE AS REQUIRED. |
| | |
| | SEC. 61G15-23.004 F.A.C. . PROCEDURES FOR DIGITALLY |
| | SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |